Type 5 – Xantrex Technology XW User Manual

Page 35

Advertising
background image

Installing the XW Automatic Generator Start

975-0307-01-01

2–13

Type 5

Type 5 is a three-wire StartStop configuration that uses relay 3 to provide
the preheat signal for Generac’s Guardian Diesel generators.

Figure 2-7 Type 5 Connection Diagram

For additional information, see
“Circuit Limitations” on page 2–5.

XW AGS Harness Wires

Generator Wires

18

17

16

14

13

12

20

19

FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY +

Relay 1

Relay 3

Relay 2

5A fuse

5A fuse

5A fuse

GENERATOR RUN SIGNAL

STOP/PREHEAT

START

GENERATOR BATTERY NEGATIVE (–)

Table 2-8 Type 5 Relay and Timing Preset Configurations

Relay Function

Preset Configuration Setting

Relay 1 mode

StartStop

Relay 3 mode

Preheat

Gen Run signal hold time

2 s

Preheat time

15 s

Preheat to crank delay

2 s

Crank time

15 s

Crank retry time

15 s

Gen Cool Down

30 s

Shutdown bypass time

0 s

Start tries

3