1 ac or dc input priority – Alpha Technologies AMP24 HP User Manual

Page 14

Advertising
background image

Doc. #: 0260011-J0 Rev B

12

DSP

400 Vdc

Boost

Telecom Grade

AC Output

DC In

AC

Mains

communication

CAN bus external

Dual redundant

synchronization

communication and

between modules

AMPS modules also have a ‘Boost’ over-current feature with 10 times the rated current capacity

for 20ms, allowing it to trip breakers downstream, thus protecting the load.

2.1.1  AC or DC input priority

The user can choose either AC or DC input priority. If AC priority is chosen, the AMPS24 HP acts

more like an on-line, double conversion UPS. If AC commercial power is available, this power is

filtered twice and passed to the AC output. If the AC commercial power fails, the DC converter

simply takes over and supplies the power from the batteries.

If DC priority is chosen, AMPS24 HP acts more like an Inverter with AC bypass function.

Normally, power is drawn from the batteries. If DC power fails, the AC-DC converter takes over,

still providing regulated and filtered power to the load.

Advertising