Doc. #: 0260011-J0 Rev B

74

7.9  Synchronization with a Maintenance Bypass Switch (MBS)

7.9.1  Internal Maintenance Bypass Switch

Implement the following sequence before switching the unit from bypass mode to inverter mode.

Switching from Bypass Mode to Inverter (On-line)

1. Switch on the

Inverter AC Input

breaker.

2. Wait for the inverters to synchronize to the line—all status LEDs on the inverters will turn green.

3. Switch on the

Inverter AC Output

breaker.

4. Smoothly rotate the maintenance bypass switch in a clockwise rotation from

BYPASS 

to

INVERTER

.

Figure 54 — Maintenance Bypass Switch

7.9.2  External Maintenance Bypass Switch

Before switching an external MBS from

UTILITY

mode to

UPS

mode:

1. Switch on the AMPS24 HP inverter input breaker. Wait for the inverters to synchronize to the line,

and for all status LEDs on the inverter modules to turn green.

2. Switch on the AMPS24 HP inverter output breaker.

3. Follow the steps in the external MBS user manual to switch the MBS bypass switch to

UPS

.