9.  System Specifications

9.1  Power De-rating Due To Altitude

The AMPS24 HP runs at full power up to an altitude of 1500 m, then derates by 8% for every 1000 m

of elevation increase. The AMPS24 HP is not designed to operate at elevations above 5000 m.

0

20

40

60

80

100

120

25

30

35

40

45

50

55

60

%

V

A

L

oa

d

Ambient Temperature (C)

DC mode Derating

9.2  Power De-rating Due To Temperature

Actual system

derating occurs

Derating alarm

triggered