Doc. #: 0260011-J0 Rev B

76

All alarm codes are listed in Table K including the following codes. They are listed here to provide

further information.

No Ethernet Communication

For a direct connection to the CXCU, verify the following:
• A cross-over cable is installed
• Wireless connection is turned off

Verify the settings of the local area network connection as follows:

1. In Windows®, select the

Start

menu,

Control Panel

, and then select

Network Connections

.

2. Right-click on the icon for the

Local Area Connection

(to be used by the laptop computer) and

then select

Properties

.

3. Make sure Internet Protocol (TCP/IP) is checked; highlight it and then select

Properties

.

4. In the Internet Protocol (TCP/IP) Properties screen, check the radio button beside

Use the 

Following IP Address

and enter or verify the following information:

• IP address: 10.10.10.202
• Subnet mask: 255.255.255.0

5. Click

OK

to close each window opened thus far.

6. At the CXCU GUI, reset the CXCU by selecting

Main Menu > Controller > Reset

.

7. Click

OK

when the reset warning pop-up window appears.

Phase Not Ready (Alarm Code 41)

Phase Not Ready alarm happens when the inverter thinks it should be in a certain phase and the

input to it is another phase. This can be corrected either by changing the input wiring to the AMPS24

HP or by changing the phase in the group mapping settings screen (see section "6.2.1 Set Output"

on page 57).

System Saturated (231)

The System Saturated alarm defaults to 80% load on the non-redundant inverters. To remove this

alarm, add more inverters or reduce the number of redundant units in

Inverters > Set Output

.

AC Mains Lost (232)

The AC Mains Lost happens when the AC input does not meet the correct voltage, phase, or

frequency. When the AC main is lost the UPS goes into inverter mode. This alarm sometimes is

accompanied by other alarms.

AC Secondary Source Lost (233)

The AC Secondary Source Lost alarm appears for either of the following events:
• Removal of DC from the system
• Incorrect settings in the group mapping screen

Refer to sections 6.2.2 and 6.2.3 to view and modify the group mapping.