4 specifications for aim 1500 module – Alpha Technologies AMP24 HP User Manual

Page 89

Advertising
background image

87

Doc. #: 0260011-J0 Rev B

9.4  Specifications for AIM 1500 Module

General specifications:

EMC (immunity)

EN 61000-4

EMC (emission)

EN55022 (Class A), FCC 47 VFR Part 15, class A

Safety

IEC 60950, UL 1778 Issue 4

Cooling

Forced Air

MTBF

240000 hrs

Efficiency (typical)

AC Input Mode

93%

DC Input Mode

90%

AC Output Power

Nominal

1500 VA

Resistive Load

1200 W

Overload Capacity (short)

150% @ 5 sec

Overload Capacity (permanent)

110%

Nominal

48 V

Range (Vdc)

40 to 60 V

Nominal Current (@40 Vdc)

33 A

Max input current (5 s)

50 A

Voltage Ripple

2 mV

AC Input Specifications

Nominal voltage (AC)

120 Vac

Voltage range (AC)

83 to 140 Vac

Power factor

> 99%

Frequency range (selectable)

60 Hz

Frequency Tolerance

± 3 Hz (Adjustable)

AC Output

Nominal (AC)*

120 Vac Accuracy 2%

Frequency

60 Hz (Same as input frequency in AC/AC mode)

Frequency accuracy

0.03%

Transient load recovery time

0.4 ms

Transfer Performance

Maximum Voltage interruption

0 sec

Total Transient voltage duration

0 sec

Environmental

Operating Temperature:

-20° to +50°C

Storage Temperature:

-20 to +70°C

Humidity:

Up to 95% non-condensing

Elevation:

<1500M

Mechanical

Dimensions H x W x D mm (in):

90 x 101.6 x 317.5 (3.5 x 4 x 12.5)

Weight kg (lb):

2.4 (5.3)

Advertising