Figure 32 — set output (split phase system) – Alpha Technologies AMP24 HP User Manual

Page 52

Advertising
background image

Doc. #: 0260011-J0 Rev B

50

23. Select

Inverters -> Set Output

to set the

number of inverters in each phase of your

system. Match the AC input phase to the

corresponding AC output phase.

a.  Number of Modules:

Enter the total

number of inverter modules that will be

installed for that phase.

b.  Redundancy:

Enter the number of

inverter modules that will provide

redundant power for that phase (used to

provide system warnings).

c.  Phase Shift

: Enter the phase shift for each output group in your system configuration

1

2

3

Single phase °

0

N/A

N/A

Split phase (120/240 V) °

0

180

N/A

2-pole (120/208) °

0

120

N/A

3-phase (120/208 V) °

0

120

240

d.  Nominal Output Voltage

: Enter

120

for all phases.

e. Press Submit.

CAUTION!

The value entered in the Nominal Output Voltage field can change the actual AC output

voltage of the inverters. Setting this value to anything other than 120 V will render the UL/

CSA approval invalid.

24. DO NOT PROCEED if there are alarms (Inverters > View Live Status).

Alarm code (41) PHASE NOT READY and/or (175) AC OUT NOT SYNCHRONIZED indicate that

the phase rotation of the AC Input is not correct. (The inverters will not start until the phase and

rotation are correct.)

To remove the alarm, return to

Inverters -> Set Output 

and correct the phases as shown:

1

2

3

2-pole (120/208 V) °

0

240

N/A

3-phase (120/208 V) °

0

240

120

25. If the alarms do not clear, go back to step 20 and repeat all steps.

Validating the inverter configuration

26. Select

Main Menu > Inverters > Group Mapping

.

27. Turn the inverters on by clicking the power icon

Turn All Modules On

(see Figure 31).

28. Switch on the Inverter AC output breaker on the front panel of the AMPS24 HP.

29. Check the actual Inverter AC Output by measuring voltages on the AC Output terminal block in

the AMPS24 HP wiring compartment:

a. The voltage from Neutral to L1 / L2 / L3 is approximately 124 V. At no load, the inverter output

voltage is slightly higher than nominal.

b. The voltage from L1 to L2 is approximately 240 V for a split phase system, 208 V for 2-pole,

or the voltage from L1 to L2, L2 to L3, L3 to L1 is approximately 208 V for a 3 phase system.

c. The voltage from AC Input L1 to AC Output L1 is less than 30 V. Similarly, the voltage

between L2 input and output and L3 input and output should be less than 30 V.

Figure 32 — Set Output (Split Phase System)