3.9.2  DC Input Groups

DC feed from the batteries to the inverters is protected by input breakers. The numbering of each DC

input breaker corresponds to the shelf it protects: DC3 input breaker, for example, protects shelf 3.

shows a four shelf, split phase system with the breakers and corresponding shelves labeled.

Figure 14 — DC input breakers

DC3 breaker

DC2 breaker

DC1 breaker

DC4 breaker

DC 1

DC2

DC 3

DC 4

Phase 1

Phase 2

Table H — DC Input Groups

Monitoring

DC Source

Bulk

Assign all inverters to DC Input Group 1.

Shelf

Assign Shelf 1 inverters to DC Input Group 1
Assign Shelf 2 inverters to DC Input Group 2
Assign Shelf 3 inverters to DC Input Group 3
Assign Shelf 4 inverters to DC Input Group 4

Dual Input

If the system has two battery strings and makes use of the dual input feature (see 5.3.3):

• Battery 1 string is fed to the inverters through breakers DC1 (shelf 1) & DC3 (shelf 3)

• Battery 2 string is fed to the inverters through breakers DC2 (shelf 2) & DC4. (shelf 4)

To monitor Battery String 1, assign all the inverters in shelves 1 & 3 to DC Input Group 1.
To monitor Battery String 2, assign all the inverters in shelves 2 & 4 to DC Input Group 2.

Configuration of the DC input

The configuration of the DC input to the inverters provides several different ways to monitor DC input

power and input current. Table H provides possible configurations.

The number of DC Input

Groups (maximum eight) is

set in the

Inverters > Group 

Mapping

screen and monitored

as a unit in the

View Group 

Status

screen.