Doc. #: 0260011-J0 Rev B

26

The recommendations in Table E are for reference only. A registered professional engineer

must review and approve or modify these recommendations in compliance with applicable

national and local electrical and building codes.

NOTE:

Table E — 21kVA, 18kVA, & 9.0kVA 120/240V Split Phase or 120/208

2-Pole 3i+1R Shelf Systems

Models

AMPS24-2-21-H2-i2

0260011-107

AMPS24-2-18-H4

0260011-106

AMPS24-2-9-H2

0260011-103

AC Input

AC Input Voltage

120/208V or 120/240V

120/208V or 120/240V 120/208V or 120/240V

Full Load AC Input Current

(per phase)

118A

121A

61A

AC Input poles & wiring

3w + G

3w + G

3w + G

Wiring

2 pole

2 pole

1 pole

SCCR

2100A

2100A

1600A

Recommended

AC input Breaker/fuse

(Note: 2)

150A

150A

80A

Recommended

AC Input Wire size,

90ºC copper (Note 1)

NEC 50ºC

2/0

2/0

3

CEC 50ºC

2/0

2/0

3

Total AC Output (Max)

21kVA/

16.8kW

18kVA/

14.4kW

9kVA/

7.2kW

AC Output

AC Output Voltage

120/208V or 120/240V

120/208V or 120/240V 120/208V or 120/240V

AC Output poles & wiring

3w + G

3w + G

3w + G

Wiring

2 pole

2 pole

1 pole

AC Output Current (per Phase)

87.5A

75A

37.5A

Installed Inverter Output

Circuit Breaker 100% rated

100A

100A

70A

Recommended

AC Input Wire size,

90ºC copper (Note 1)

NEC 50ºC

2/0

2/0

3

CEC 50ºC

2/0

2/0

3

AC Input & Output

connection terminals

Box lugs are rated for both Aluminum or Copper wire, #2/0 to

#6 AWG. Fasten clamping screw to 120 in-lbs (14 N-m)

Advertising