Models, Ac input, Ac output – Alpha Technologies AMP24 HP User Manual

Page 26

Advertising
background image

Doc. #: 0260011-J0 Rev B

24

The recommendations in Table D are for reference only. A registered professional engineer

must review and approve or modify these recommendations in compliance with applicable

national and local electrical and building codes.

NOTE:

Table D — 12kVA and 6kVA, 120V Single Phase, 4i Shelf

Systems

Models

AMPS24-2-12-i2

#0260012-203/202

AMPS24-1-6-i1

#0260012-201

AC Input

AC Input Voltage

120V

120V

Full Load AC Input Current

(per phase)

106A

53A

AC Input poles & wiring

2w +G

2w +G

Wiring

1 pole

1 pole

SCCR

2100A

1600A

Recommended

AC input Breaker/fuse

(Note: 2)

150A

70A

Recommended

AC Input Wire size,

90ºC copper (Note 1)

NEC 50ºC

1

6

CEC 50ºC

1/0

4

Total AC Output (Max)

12kVA/

9.6kW

6kVA/

4.8kW

AC Output

AC Output Voltage

120V

120V

AC Output poles & wiring

2w +G

2w +G

Wiring

1 pole

1 pole

AC Output Current (per Phase)

100A

50A

Installed Inverter Output

Circuit Breaker 100% rated

100A

70A

Recommended

AC Input Wire size,

90ºC copper (Note 1)

NEC 50ºC

1

6

CEC 50ºC

1/0

4

AC Input & Output

connection terminals

Box lugs are rated for both Aluminum and Copper wire, #2/0 to #6

AWG. Fasten clamping screw to 120 in-lbs (14 N-m)

Note 1: Inverter AC Input & AC Output connections: Calculations based on full load and charging current, 0.8

derating with 5 current carrying conductors, (L1,L2,L3,2xN) due to possible high harmonic content load.

Temperature correction factor for 50C applied.

Note 2: Maximum AC Utility Service protection feeding the AMPS24 is 150A. Actual supply circuit breaker must

be sized appropriately for the supply wire used. Consult your local and national electrical codes. Double

neutral is strongly recommended for AC output wiring (and AC input wiring to the MBS) for 3Ф systems with

significant non-linear (ie rectified capacitive) loads. Since the AC input to systems without MBS is power

factor corrected, AC wiring to systems without MBS does not require double neutral wiring.