3 inverter module indicators, Figure 48 — inverter module status, power leds, Figure 49 — output power indicator leds – Alpha Technologies AMP24 HP User Manual

Page 65: 1 status leds

Advertising
background image

63

Doc. #: 0260011-J0 Rev B

6.3  Inverter Module Indicators

6.3.1  Status LEDs

Inverter Status LED

Description

Remedial action

OFF

No power or forced stop

Check AC input

Permanent green

Input OK, normal operation

None required

Flashing green

Inverter OK but conditions are not

within normal parameters

Check upstream and surrounding

equipment

Flashing green/orange alternating Recovery mode after boost

(10 In short circuit condition)

Wait for a while

Permanent orange

Starting-up mode

Wait

Flashing orange

Modules cannot start

Insert CXCU

Flashing red

Recoverable fault

Wait or attempt to clear fault condition by

removing and reinserting the module

Permanent red

Non recoverable fault

• Attempt to clear fault condition by

removing and reinserting the module

• Download CXCU inverter alarm logs

(see section 10.1)

• Record the alarm(s)
• Send module back for repair

Output Power (redundancy not counted)

The output power LEDs (located on the right side of the module’s front panel indicate the amount of

power (percentage of rated power) provided by the module. The number of bars that are illuminated

combined with whether or not they are on steady or flashing indicate the output power level or

overload condition as shown in Figure 49.

Output power

indicator LEDs

Status LEDs

Figure 48 — Inverter module status, power LEDs

AC input

AC output

DC input

< 5%

Flashing

5% to 40%

On steady

40% to 70%

On steady

80% to 95%

On steady

100%

On steady

100% Overload

Flashing

Figure 49 — Output power indicator LEDs