Models, Ac input, Ac output – Alpha Technologies AMP24 HP User Manual

Page 25

Advertising
background image

23

Doc. #: 0260011-J0 Rev B

The recommendations in Table C are for reference only. A registered professional engineer

must review and approve or modify these recommendations in compliance with applicable

national and local electrical and building codes.

NOTE:

Table C — 10.5kVA, 9kVA and 4.5kVA, 120V Single Phase 3i+1R Shelf

Systems

Models

AMPS24-1-10.5-H1-i1

#0260011-104

AMPS24-1-9-H2

#0260011-102

AMPS24-1-4.5-H1

#0260011-101

AC Input

AC Input Voltage

120V

120V

120V

Full Load AC Input Current

(per phase)

108A

108A

54A

AC Input poles & wiring

2w +G

2w + G

2w + G

Wiring

1 pole

1 pole

1 pole

SCCR

2100A

2100A

1600A

Recommended

AC input Breaker/fuse

(Note: 2)

125A

120A

70A

Recommended

AC Input Wire size,

90ºC copper (Note 1)

NEC

50ºC

1

1/0

6

CEC

50ºC

1/0

1/0

4

Total AC Output (Max)

10.5kVA/

8.4kW

9kVA/7.2kW

4.5kVA/3.6kW

AC Output

AC Output Voltage

120V

120V

120V

AC Output poles & wiring

2w +G

2w +G

2w +G

Wiring

1 pole

1 pole

1 pole

AC Output Current (per Phase)

87.5A

75A

37.5A

Installed Inverter Output

Circuit Breaker 100% rated

100A

100A

70A

Recommended

AC Input Wire size,

90ºC copper (Note 1)

NEC

50ºC

1

1

6

CEC

50ºC

1/0

1/0

4

AC Input & Output

connection terminals

Box lugs are rated for both Aluminum and Copper wire, #2/0 to #6 AWG. Fasten

clamping screw to 120 in-lbs (14 N-m)