Alpha Technologies AMP24 HP User Manual

Page 98

Advertising
background image

Doc. #: 0260011-J0 Rev B

96

;290;

;DC 4 : Vdc_in Low Start;

;49; ;V;

;291;

;DC 4 : Vdc_in Low Transfer;

;42; ;V;

;292;

;DC 4 : Vdc_in Low Stop;

;42; ;V;

;293;

;DC 4 : Vdc_in High Start;

;58; ;V;

;294;

;DC 4 : Vdc_in High Transfer;

;61; ;V;

;295;

;DC 4 : Vdc_in High Stop;

;61; ;V;

x

The same as Group DC 1

;300;

;DC 5 : Vdc_in Low Start;

;49; ;V;

;301;

;DC 5 : Vdc_in Low Transfer;

;42; ;V;

;302;

;DC 5 : Vdc_in Low Stop;

;42; ;V;

;303;

;DC 5 : Vdc_in High Start;

;58; ;V;

;304;

;DC 5 : Vdc_in High Transfer;

;61; ;V;

;305;

;DC 5 : Vdc_in High Stop;

;61; ;V;

x

The same as Group DC 1

Synchronization with ACin source

;370;

;AC : Fac_in Low Start;

; 57.3; ;Hz;

x

Below this value and above parameter 371, the inverters will try to synchronize with the

ACin frequency

;371;

;AC : Fac_in Low Stop;

;57.0; ;Hz;

x

Below this value the inverters will stop trying to synchronize with the ACin frequency

;372;

;AC : Fac_in High Start;

;62.7; ;Hz;

x

Above this value and less than parameter 375, the inverters will try to synchronize with the

ACin frequency

;375;

;AC : Fac_in High Stop;

;63; ;Hz;

x

Above this value, the inverters will trying stop to synchronize with ACin

Parameters for AC Groups

;380;

;AC 1 : Vac_in Low Start;

;91.5; ;V;

x

ACin Voltage where a higher value causes the converter AC/AC to start

x

Range: 83 to 143, default: 91.5 V

Advertising