9.3  System Specifications

System AC Input (P/N 0140004)

Nominal Voltage (AC)

120 V

Input Power Factor

>99%

Frequency

60 Hz

Synchronization Range

57-63 Hz

System DC Input

Nominal Voltage

48 Vdc

Voltage Range (max)

40-60 Vdc (user adjustable)

Max DC input current @ 48 Vdc

389 A

Max DC input current @ 40 Vdc

467 A

Unified System Controller with SNMP

Control & Monitoring

Configure, control and monitor Inverter & Rectifier modules

via Internet Explorer 7 and onwards

Display

LCD Touchscreen display

OK / Major / Minor 3-color LED display

Web-based GUI via Ethernet

Communication Ports

RJ45 Ethernet Port

Controller I/O

Voltage Inputs

0

Temperature Inputs

2

Current Inputs

1

Bivoltage Inputs

0

Digital Inputs

2

Relay Outputs

6

Environmental Specifications

Operating Temperature (full load)

-20° to 50°C (-4° to 122°F)

Storage Temperature

-40° to 70°C (-40° to 158°F)

Relative Humidity

Up to 95%, non-condensing

Operating Altitude

Up to 1,500 m (4,900 ft) above sea level

Heat Dissipation Per Module

286 BTU/hr in AC-to-AC mode

410 BTU/hr in DC-to-AC mode

Mechanical Specifications

No of shelves

System Dimensions H x W* x D

mm (in)

System Weight -- without modules

kg (lb)

4

622 x 443 x 432 (24.5 x 17.44 x 17)

52 (115)

3

533 x 443 x 432 (21 x 17.44 x 17)

45 (100)

2

444.5 x 443 x 432 (21 x 17.44 x 17)

39 (85)

1

355.6 x 443 x 432 (21 x 17.44 x 17)

32 (70)

*Width with mounting ears

19" rack mount option: 492.8mm/ 19.4"

23" rack mount option: 584.2mm/ 23"

Agency Compliance

CSA

C22.2 107.3-05

UL

UL1778; Issue 4

(shelves and modules)

EMC

FCC CFR47 Part 15 Class A; ICES-003