Figure 38 — set output window, 1 set output – Alpha Technologies AMP24 HP User Manual

Page 59

Advertising
background image

57

Doc. #: 0260011-J0 Rev B

6.2.1  Set Output 

Number of

modules:

The value is the number to be acquired by the CXCU. An invalid setting will result in an

alarm condition:

Inverter Comms Lost

; i.e., the number of modules must agree with the

actual number of inverters mapped to that particular group.

Amount of

Redundancy:

Number of inverters considered redundant

Phase shift:

Assign a phase shift (in degrees) to the AC output group

1

2

3

Single phase

0

N/A

N/A

Split phase (120/240 V)

0

180

N/A

2-pole (120/208 V)

0

120

N/A

3-phase (120/208 V)

0

120

240

If the actual phase rotation of the AC Input is not 1 – 2 – 3 (i.e. it may be 1 – 3 – 2),

alarms will result. See NOTE below.

Nominal Output

Voltage

Sets the target output AC voltage and must be used with caution; the devices

connected to the inverters could sustain damage due to irregular AC voltage.

Verify that the Phase Shift is set correctly before

mapping inverters in the new groups and turning

them on.

Figure 38 — Set Output window

Alarm code (41) PHASE NOT READY and/or (175) AC OUT NOT SYNCHRONIZED indicate that the phase

rotation of the AC Input is not correct. (The inverters will not start until the phase and rotation are correct.)

To remove the alarm, return to

Inverters -> Set Output 

and correct the phases as shown:

1

2

3

2-pole (120/208 V) °

0

240

N/A

3-phase (120/208 V) °

0

240

120

NOTE:

CAUTION!

The value entered in the Nominal Output Voltage field can change the actual AC output

voltage of the inverters. Setting this value to anything other than 120 V will render the UL/

CSA approval invalid.