Figure 16 — AMPS24 Power and Battery Connections

Notes

1. All wiring must be in accordance with applicable electrical codes.

2. A low voltage battery disconnect (LVBD) should be provided with the battery system.

3. Inverter main input must always include a neutral connection.

4. Power and control cables must be in separate conduits.

5. N-G shorting jumper is factory installed for inverter systems only. Remove if AC input neutral is

connected. (Refer to note in Figure 16.)

6. L3 is only used with 3-phase systems.

7. Two independent battery strings can be connected. Tie bars are provided for single or dual DC

feed. (Refer to note in Figure 16.)

Carefully review the following schematic and notes 1 through 7 before beginning the AC input and

output, and DC wiring.