2.5  Battery Temperature Probes

Adjusting the battery’s float or equalize voltage to

correspond with temperature fluctuations ensures

maximum battery performance and life expectancy.

The CXC’s built-in automatic temperature

compensation function adjusts the system every ten

minutes as the temperature changes and changes the

voltage by a maximum of 0.1 V during this interval.

A battery probe from a single string can be connected

to pins #18 and #20 of the AMPS24 HP 40-pin

connector. Figure 6 shows the connection of two

battery probes where pins #14 and #16 are used for

the second probe.

Connection Procedure

1. Use needle nose pliers to remove the terminal

block.

2. Connect the battery temperature probes,

3. To calibrate the temperature probes, refer to

Analog Signal Calibration in the CXCU manual or

to the alpha website (www.alpha.ca): Technical 

Documentation > Method of Procedures 
> Cordex > Controller > Calibration – 
Temperature

(web interface).

4. Complete the

Batteries > Battery Properties

parameters to enable the Temperature

Figure 6 — Battery temperature probes

Figure 7 — Batteries > Configure Batteries

Compensation feature. The Battery Properties window contains information provided by the

battery manufacturer.

5. Set up temperature compensation in

Batteries > Configure Batteries

—see Figure 7.