2 system components, Figure 1 — amps24 hp system components – Alpha Technologies AMP24 HP User Manual

Page 15

Advertising
background image

13

Doc. #: 0260011-J0 Rev B

2.2  System Components

The AMPS24 HP is made up of a number of individual subsystems designed to work together to

provide highly reliable, filtered power in support of the load. A typical system contains the following:

1. Inverter AC Input Breaker: Main disconnect for AC input

2. Internal Maintenance Bypass Switch (MBS) (optional): Can be used to route power directly

from the AC input to the AC output, bypassing the inverter modules.

3. Inverter AC Output Breaker: Serves as the main disconnect for the inverter AC outputs.

4. Graphic display touch screen: Connected to the CXCU controller by cable (see figure)

5. RJ45 cable connector: Front panel connection for cable from the CXCU to the Graphic display

6. CXCU Unified System Controller with integrated Ethernet/ SNMP: Monitors and manages

both inverter and rectifier modules through a web-based GUI (only 1 per unit).

7. DC Input Breakers: Individual DC input breakers for each shelf.

8. 4i or 3i+1R shelves: Up to four shelves for installing up to four hot-swappable AIM 1500

modules OR three AIM 1500 modules plus one 1800W rectifier per shelf.

9. AIM 1500 Modules: Up to 4 AIM 1500 per 4i (4 x inverter modules) shelf or up to 3 AIM 1500

per 3i+1R (3 x inverter modules and 1 x rectifier module) shelf.

5

1

11

12

10

13

3

2

7

6

4

8

9

Figure 1 — AMPS24 HP System Components

Advertising