Alpha Technologies AMP24 HP User Manual

Page 32

Advertising
background image

Doc. #: 0260011-J0 Rev B

30

3.8  AMPS24 HP - Recommended DC Breaker and Wire Sizes

The recommendations in this table are for reference only. A registered professional engi-

neer must review and approve or modify these recommendations in compliance with appli-

cable national and local electrical and building codes.

NOTE:

Maximum wire gauge size is 350 kcmil; 4/0 or smaller is recommended, 90

°

C or better copper only.

Model

Recommended minimum DC Breaker

rating (100% rated per feed),

Maximum DC Input

Wattage

Maximum DC

Input Current @

48Vdc, full load

Single DC feed

Dual DC feed

AMPS24-2-24

x

300

21.4 kW

480 A

AMPS24-2-21

x

250

18.7 kW

406 A

AMPS24-2-18

x

225

16 kW

333 A

AMPS24-2-9

250

125

8 kW

166 A

AMPS24-2-12

300

150

10.7 kW

240 A

AMPS24-3-18

x

225

16 kW

350 A

AMPS24-3-13.5

350

175

15 kW

250 A

AMPS24-1-10.5

250

125

9.4 kW

203 A

AMPS24-1-12

300

150

10.7 kW

240 A

AMPS24-1-9

250

125

8 kW

166 A

AMPS24-1-6

150

75

5.4 kW

120 A

AMPS24-1-4.5

120

60

4 kW

83 A

Torque specifications for DC wiring (3/8" bolts that attach the DC lugs at the back of the DC

distribution box) are as follows:

• Imperial: 190 – 240 inch/lbs
• Metric: 21.5 – 27.1 N-m

Advertising