Table k — inverter alarm codes – Alpha Technologies AMP24 HP User Manual

Page 83

Advertising
background image

81

Doc. #: 0260011-J0 Rev B

Table K — Inverter Alarm Codes

Alarm Type

Description

Cause

Solution

80

BROWNOUT

DERATING

The nominal power is not

available from the AC

Grid. The inverter could

compensate from DC

source.

AC in below 100V - reduce

power from the AC input and

pull power from the DC input

Check AC grid and

configuration

81

FAN LIFE

ELAPSED

Fan running time has exceeded preset value to advise fan

replacement

Replace FAN and reset the

counter time

82

REMOTE OFF Inverters are set to OFF

remotely

Inverter are switch OFF by

remote function

Replace FAN and actualize

the counter time

83

MANUALLY OFF The inverter are manually

set to OFF.

Inverter are switched OFF

by the OFF function in

Hyperterminal

Start inverter by REM ON/

OFF terminal

Start inverter through the

Hyperterminal

Status AC on Inverter

160 ACin OK

The grid AC is coming back

inside the preset range

AC voltage coming back

inside the range

Nothing to do

161 Vac_in too low

The input grid is below the

preset range

AC voltage outside the range Check AC grid and

configuration

162 Vac_in too high

The input grid is upper the

preset range

AC voltage outside the range Check AC grid and

configuration

163 ACin IMP too

high

This status appears during

the starting procedure of the

ACinput stage

The module can stay in this

status if it can't start. This

happens if the power of the

AC supply is too low

164 STATUS 164
165 Vac_in too LOW The input grid is below the

preset range

AC voltage outside the range

(RMS value)

Check AC grid and

configuration

166 Vac_in too HIGH The input grid is above the

preset range

AC voltage outside the range

(RMS value)

Check AC grid and

configuration

167 ACin NOT

CONFORM

ACin is outside the range

AC voltage outside the range

(instantaneous value)

Check AC grid and

configuration

168 ACin NOT

CONFORM

ACin is outside the range

AC voltage outside the range

(instantaneous value)

Check AC grid and

configuration

169 ACin NOT

CONFORM

ACin is outside the range

AC voltage outside the range

(instantaneous value)

Check AC grid and

configuration

170 STATUS 170
171 ACin NOT

CONFORM

ACin is outside the range

AC voltage outside the range

(instantaneous value)

Check AC grid and

configuration

172 ACin THD too

high

THD grid is outside the

allowed value

THD AC voltage outside the

range

Check AC grid THD

173 STATUS 173
174 STATUS 174
175 ACout NOT

SYNC

The AC out is not

synchronized with grid

Check synchronization

between AC in and AC out

Check AC grid and

configuration

176 INV NOT SYNC The AC out is not

synchronized with grid

Check synchronization

between AC in and AC out

Check AC grid and

configuration

177 SYNC FAILURE Inverter not synchronized

Check synchronization

between AC in and AC out

Check AC grid and

configuration

Advertising