4 over temperature protection, 5 wide ac range, 6 ac inrush/transient suppression – Alpha Technologies AMP24 HP User Manual

Page 68: 7 soft start, 8 start delay, 9 current limit/short circuit protection

Advertising
background image

Doc. #: 0260011-J0 Rev B

66

6.4.4  Over Temperature Protection

Each rectifier module is protected against an excessive increase in temperature caused by a component

failure or a cooling airflow blockage. During over-temperature conditions, the rectifier limits the output

power and the output current. If the temperature continues to increase, a shutdown of the rectifier is

initiated. The rectifier restarts automatically when the temperature returns to a safe level.

6.4.5  Wide AC Range

A minor alarm is generated when the AC input voltage drops below its allowable limit. The rectifier output

power is reduced linearly between 187 Vac and 90 Vac. At 90 Vac, the unit delivers derated output power

that is more than 33% of the rated output power.

Below 90 Vac, the module shuts down and restarts only when the AC voltage is greater than 95 Vac.

The actualrestart voltage depends on the load current. A reduced load current may allow a restart input

voltage as low as 100 Vac.

For voltages above 277 Vac, the power factor and total harmonic distortion may be derated. Up to 312

Vac (320 Vac for the 1.8 rectifier), the rectifier is operational and will not suffer any damage.

6.4.6  AC Inrush/Transient Suppression

To prevent a surge on the AC input line, the inrush current of a rectifier module is limited to the full

load steady state line current. Modules are also protected from input lightning and transient surges in

accordance with IEEE/ANSI C62.41 Category B3 standards.

6.4.7  Soft Start

A soft start feature is used to eliminate an instantaneous demand on the AC power source. A soft start,

sometimes referred to as a “current walk-in”, works by gradually (up to five seconds) ramping up the

current limit from zero to the actual or defined customer setting. The rectifier output voltage is ramped

from the minimum voltage to the float voltage.

6.4.8  Start Delay

The rectifier modules are equipped with a delay timer to stagger-start a series of modules to prevent

excessive loading of generators upon start up. The built-in timer delays the switching on of the module by

an interval (up to 120 seconds), which is set in the CXC. A minimum one-second delay is preset to allow

the input capacitors to charge.

6.4.9  Current Limit/Short Circuit Protection

The current limit function determines the maximum output current limit of the rectifier module, regardless

of the output voltage or power. The maximum output current is limited to a constant value down to a short

circuit condition. Current limiting can be used to mate the rectifier output current ampacity to the needs of

the load and parallel battery to minimize excessive battery recharge currents.

The rectifier will sustain a short circuit at the output terminals indefinitely. The maximum short circuit

current will not exceed 105% of the rated full load current.

Advertising