3 global settings (id 1 – 50) – Alpha Technologies AMP24 HP User Manual

Page 93

Advertising
background image

91

Doc. #: 0260011-J0 Rev B

10.3  Global Settings (ID 1 – 50)

;1;

;Number of inverter modules in phase 1;

;4;

;2;

;Number of inverter modules in phase 2;

;4;

;3;

;Number of inverter modules in phase 3;

;4;

x

Number of inverters present (Here shown as 4 modules) in each phase

x

Range: 0 - 32, Default: 1

x

min:0 1 32

x

(same value for AC

in

and AC

out

)

;21;

;Amount of redundancy in phase 1;

;1;

;22;

;Amount of redundancy in phase 2;

;1;

;23;

;Amount of redundancy in phase 3;

;1;

x

Number of redundant inverters in each phase (Here shown as 1 module)

x

Range: 0 - 32, Default: 0

x

When no inverter failed = no alarm

x

When # of inverters failed ≤ redundancy (if different than 0) = Minor alarm (non urgent)

x

When # of inverters failed > redundancy = Major alarm (urgent)

;40;

;Number of DC input groups;

;1;

x

Number of DC input groups

x

Range: 1 - 8, Default: 1

x

Allows inverters groups to be supplied from sets of batteries that are physically separated

;41;

;Number of AC input groups;

;1;

x

Number of AC input groups

x

Range: 1 - 4, Default: 1