10.3 Global Settings (ID 1 – 50)
;1;
;Number of inverter modules in phase 1;
;4;
;2;
;Number of inverter modules in phase 2;
;4;
;3;
;Number of inverter modules in phase 3;
;4;
x
Number of inverters present (Here shown as 4 modules) in each phase
x
Range: 0 - 32, Default: 1
x
min:0 1 32
x
(same value for AC
in
and AC
out
)
;21;
;Amount of redundancy in phase 1;
;1;
;22;
;Amount of redundancy in phase 2;
;1;
;23;
;Amount of redundancy in phase 3;
;1;
x
Number of redundant inverters in each phase (Here shown as 1 module)
x
Range: 0 - 32, Default: 0
x
When no inverter failed = no alarm
x
When # of inverters failed ≤ redundancy (if different than 0) = Minor alarm (non urgent)
x
When # of inverters failed > redundancy = Major alarm (urgent)
;40;
;Number of DC input groups;
;1;
x
Number of DC input groups
x
Range: 1 - 8, Default: 1
x
Allows inverters groups to be supplied from sets of batteries that are physically separated
;41;
;Number of AC input groups;
;1;
x
Number of AC input groups
x
Range: 1 - 4, Default: 1