10.2.2  Changing the Synchronization Tracking Speed Operation

This parameter sets the speed with which the module tries to synchronize ACout.

1. Save the inverter configuration file to a local disk (

Main Menu > Inverters > Manage Config File

).

2. Open the file with a text editor.

3. Scroll down to Synchronization Tracking Speed

;100; ;Synchronization Tracking Speed; ;0; ; ;

4. Change the default to one of the values from the following table:

Value

Tracking speed, Hz/sec

-2

2

-1

1

0

0.5

+1

0.25

+2

0.1

5. Save the file to the local disk.

6. Upload to the inverter system.

7. Save the inverter configuration file to the local disk with a different name than before.

10.2.3  Changing the Walk-in Mode for Generator Operation

Walk-in mode needs to be set if a generator is used in bypass mode. Walk in mode stops the

oscillation that causes DC mode to activate. It allows a progressive comeback, slowly removing DC

power while slowly increasing AC power.

1. Save the inverter configuration file to a local disk (

Main Menu > Inverters > Manage Config File

).

2. Open the file with a text editor.

3. Scroll down to Walk-in Mode

;62; ;Walk-in Mode (0 : No, 1 : Yes); ;0; ; ;

4. Set the parameter to 1.

5. Save the file to the local disk.

6. Upload to the inverter system.

7. Save the inverter configuration file to the local disk with a different name than before.