X-sel i/o parameter, B. when only two cc-link boards are used, C. when only one cc-link board is used – IAI America E-Con User Manual

Page 61

Advertising
background image

53

3. X-SEL-J/K/P/Q/JX/KX/PX/QX

X-SEL I/O parameter

No. Parameter

name

Default

(reference)

Input

range

Setting Remarks

1

I/O port assignment type

1

0 – 20

01

0: Fixed assignment

1: Automatic assignment (Priority: slot 1

᫦)

* The ports only in the continuous installation

range from slot 1 are assigned for safety.)

2

Standard I/O fixed assignment time:

Input port start No. (I/O 1)

-1

-1 – 599

-1

0 + (multiples of 8) (Invalid for negative values)

3

Standard I/O fixed assignment time:

Output port start No. (I/O 1)

-1

-1 – 599

-1

300 + (multiples of 8)

(Invalid for negative values)

4

Expansion I/O 1 fixed assignment

time: Input port start No. (I/O 2)

032

-1 – 599

032

0 + (multiples of 8) (Invalid for negative values)

(Slot next to the standard I/O)

5

Expansion I/O 1 fixed assignment

time: Output port start No. (I/O 2)

332

-1 – 599

332

300 + (multiples of 8)

(Invalid for negative values)

6

Expansion I/O 2 fixed assignment

time: Input port start No. (I/O 3)

016

-1 – 599

016

0 + (multiples of 8) (Invalid for negative values)

7

Expansion I/O 2 fixed assignment

time: Output port start No. (I/O 3)

316

-1 – 599

316

300 + (multiples of 8)

(Invalid for negative values)

8

Expansion I/O 3 fixed assignment

time: Input port start No. (I/O 4)

000

-1 – 599

000

0 + (multiples of 8) (Invalid for negative values)

9

Expansion I/O 3 fixed assignment

time: Output port start No. (I/O 4)

300

-1 – 599

300

300 + (multiples of 8)

(Invalid for negative values)

10 Standard I/O error monitoring

(I/O 1)

0

0 – 5

0

11

Expansion I/O 1 error monitoring

(I/O 2)

2

0 – 5

2

12 Expansion I/O 2 error monitoring

(I/O 3)

2

0 – 5

2

13 Expansion I/O 3 error monitoring

(I/O 4)

2

0 – 5

2

0: Non-monitoring

1: Monitoring

2: Monitoring (Non-monitoring of 24V I/O power

related errors)

(Main application of Ver. 0.55 or later)

3: Monitoring (Monitoring of 24V I/O power

related errors only)

(Main application of Ver. 0.55 or later)

14 Network I/F card remote:

Number of ports used for input

0

0 – 256

0

Multiples of 8

15 Network I/F card remote:

Number of ports used for output

0

0 – 256

0

Multiples of 8

(I/O 1) to (I/O 4) indicate the slot numbers.

b.

When only two CC-Link boards are used

The I/O 2 (expansion I/O 1) slot becomes empty. Accordingly, both the default and set value become “-1” for

the I/O parameter No. 4 and No. 5 and “0” for No. 11 in the table above.

(The above is a case where the installation condition as shown in Fig. 3-2-2 in section 3.2.1 is applied.)

c.

When only one CC-Link board is used

The I/O 2 (expansion I/O 1) and I/O 3 (expansion I/O 2) slots become empty. Accordingly, both the default

and set value become “-1” for the I/O parameters No. 4 to No. 7 and “0” for No. 11 and No. 12 in the table

above.

(The above is a case where the installation condition as shown in Fig. 3-2-1 in section 3.2.1 is applied.)

(Note) When no I/O board is used, it is not required to supply 24V DC to the I/O 24V power connector. In any case of a, b, and c

above, set the I/O parameter No. 10 to “0.”