4. XSEL-R/S/RX/SX/RXD/SXD

[1] Network Setting Check

Confirm that the 2nd digit of I/O Parameter No. 25 Network I/F Module Control setting is showing
“1” (CC-Link).

No.

Parameter name

Default

Input Range

Unit

Remarks

225

Network I/F
Module Control

1*

10H to 13H

-

bits 4-7(2

nd

digit):

Network I/F Module 2type

0: Not Mounted
1:CC-Link
2:DeviceNet
3:PROFIBUS

[2]

I/O

Port Allocation

Type

I/O Parameter No.1

Set I/O Port Assignment Classification.

No.

Parameter name

Default

Input Range

Unit

Remarks

1

I/O Port Assignment
Classification Setting

(Note)

1

0 to 1

-

0: Fixed Allocation
1: Automatic Allocation

x

Reference Priority of I/O Port

Assignment when
automatically assigned

1) to Port Number

(No.0 to 299/No.300 to

599)

2) Network I/F Module1
3) I/Oslot 1(I/O1) Mounting

board

4) I/Oslot 2(I/O2) Mounting

board

* I/Oslot 1(I/O1) Assigned for

the continuously mounted
range from mounting board

x

Reference Priority of I/O Port

Assignment when
automatically assigned

1) to Port Number

(No.1000 to 3999/No.4000

tp 6999)

2) Network I/F Module 2
3) Expansion I/O unit
4) IA Net

Note If the automatic assignment is selected, the input port is assigned to an extension

input port domain (No. 1000 to 3999). The output port is assigned to an extension
output port domain (No. 4000 to 6999).

If the fixed assignment is selected, the user will manually assign the input to either of the
standard input port domain (No. 0 to 299) or extension input port domain (No. 1000 to
3999). For the output port, the user will manually assign the output to either the standard
output port domain (No. 300 to 599) or the extension output port domain

(No. 4000 to

6999).

Reference

Priority of I/O Port
Assignment when
automatically assigned
Port Number
(No.0 to 299/No.300 to 599)

1) Network I/F Module1
2) I/O slot 1 (I/O1) Mounting

board

3) I/O slot 2 (I/O2) Mounting

board

* I/O slot 1 (I/O1) Assigned for

the continuously mounted
range from mounting board

1)
2)
3)

Reference

Priority of extension I/O ports
at automatic assignment
Port Number
(No.1000 to 3999/No.4000 to
6999)

Confirm that the 2nd digit of I/O Parameter No. 225 Network I/F Module Control setting is
showing “1” (CC-Link).

I/O Port Allocation Type Setting

Note If the automatic assignment is selected, the input port is assigned to an extension

input port area (No. 1000 to 3999). The output port is assigned to an extension
output port area (No. 4000 to 6999).
If the fixed assignment is selected, the user will manually assign the input to either
of the standard input port area (No. 0 to 299) or extension input port area (No. 1000
to 3999).
For the output port, the user will manually assign the output to either the standard
output port area (No. 300 to 599) or the extension output port area (No. 4000 to
6999).