4. XSEL-R/S/RX/SX/RXD/SXD

[3] CC-Link Board Use Setting

Set “1” (Monitoring: use CC-Link board) to I/O Parameter No. 235.

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

235

Network I/F Module Error
Monitoring

1

0 to 5

-

0: No Monitoring

(Not to monitor condition of link
to PLC (master))

1: Monitoring

[4]

Node

address

setting

Set the node address to I/O Parameter No. 237

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

237

Network I/F Module 2
Node Address

0

0 to 64

-

CC-Link node address range:

1 to 64

Note If

a

number

out of the settable range is selected, “D75: Fieldbus Parameter Error” will

occur.

[5] Communication

Speed Setting

Set the communication speed in I/O Parameter No. 238. Match the setting to the communication
speed of the master unit.

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

238

Network I/F Module 2
Baud rate

0

0 to 4

-

0: 156Kbps
1: 625Kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps

Note If a number out of the settable range is selected, “D75: Fieldbus Parameter Error” will

occur.

[6] Number of I/O Port Setting

Set the number of ports to be used for I/O Parameters No. 231 to 232.

Note Set a number that is a multiple of 8.

No.

Parameter name

Default

(Reference)

Input Range

Unit

Remarks

231

Network I/F Module 2
Remote Input Ports

0

0 to 256

-

8 port unit

232

Network I/F Module 2
Remote Output Ports

0

0 to 256

-

8 port unit

Network I/F Module 2 Error
Monitoring

Node Address Setting

Baud Rate Setting

Network I/F Module 2
Baud Rate

No. of Network I/F Module 2
Remote Input Ports
No. of Network I/F Module 2
Remote Output Ports