<2. Connection>

2-3

IM 01C25R02-01E

(1) Confirming the device revision of the transmitter

● Confirmation by using integral indicator

(When the integral indicator code is “D”)

Refer to the section 2.1

● Confirmation by using HART configuration

tool

Follow the procedure below.

1) Connect the configuration tool to the

transmitter.

2) Select the “Root Menu” (Refer to

subsection 3.1.1)

Call up the “Review” display.

3) The device revision is displayed on the

“Fld dev rev” column.

(2) Confirming the device revision of the

configuration tool

Confirm the device revision from the installed

DD file name according to the procedure

provided for the configuration tool.

The first two digits indicate the device revision

and the next two digits indicate the DD revision.

0 a 0 1. X X X

DD revision
Device revision

NOTE

Device revision of DD file is given in hexadecimal

2.4 Set the parameters using

DTM

When configure the parameters using FieldMate,

use the DTM (Device Type Manager) shown in the

Table 2.2.

Table 2.2

HART Protocol Revision and DTM

HART

Protocol

Revision

DTM

EJX multivariable transmitters

Name

Revision

Model

Name

Device

Type

Device

Revision

5

EJX910
V2.1

1.4.160.27*

1

or later

EJX910A
EJX930A

EJX910
(0x54)

2

7

EJX910
HART 7
DTM

3.3.0.112*

2

or later

EJX910A
EJX930A

EJX910_
EXP
(0x3754)

10

*1: The DTM corresponding to this revision is included in

Yokogawa DTM Library HART 2011-3/Device Files R3.03.00

*2: The DTM corresponding to this revision is included in

Yokogawa Device DTM Library 2.0/Device Files R3.03.00

NOTE

The DTM revision can be confirmed by “DTM

setup”.

Device Files is a Media included in FieldMate.

The user registration site provides Device Files

with the latest update programs.

(URL: https://voc.yokogawa.co.jp/PMK/)

In case update, following operation by “DTM

setup” is required.

• Update DTM catalog

• Assign corresponding DTM to the device

(refer to Table 2.2)

Refer to FieldMate Instruction Manual for detail.

2.5 Interconnection Between

DPharp and the HART

Configuration Tool

The HART configuration tool can interface with the

transmitter from the control room, the transmitter

site, or any other wiring termination point in the

loop, provided there is a minimum of 250 Ω

between the connection and the power supply. To

communicate, it must be connected in parallel with

the transmitter; the connections are non-polarized.

Figure 2.2 illustrates the wiring connections for

direct interface at the transmitter site for the

DPharp. The HART configuration tool can be used

for remote access from any terminal strip as well.

USB

FieldMate

Modem

Relaying

terminals

Distributor

Control room

Terminal

board

F0202.ai

USB

PC/FieldMate

HART configuration tool

DPharp

SUPPL

Y

PULSE

CHECK

ALARM

Figure 2.2

Connecting the HART Configuration

Tool