Yokogawa EJX930A User Manual

Page 86

Advertising
background image

<5. Parameter Summary>

5-4

IM 01C25R02-01E

Function

Label

Item

Contents

Default value Handling

*

1

Display setup Bar Indicator

Bar indicator

Off or On

On

W

Disp Out 1/Disp1

LCD output 1

PV %, Flow, Pres, SP, EXT.

TEMP, ENGR.PV, or TOTAL

FLOW

PV %

W

Disp Out 2/Disp2

LCD output 2

PV %, Flow, Pres, SP, EXT.

TEMP, ENGR.PV, TOTAL

FLOW, or Not used

Not used

W

Disp Out 3/Disp3

LCD output 3

(Ditto)

Not used

W

Disp Out 4/Disp4

LCD output 4

(Ditto)

Not used

W

Disp % Reso

% display resolution

Normal or High resolution

Normal

W

Engr exp

User set exponent

---, x10, x100, x1000

--- or as

specified

W

Engr LRV

User set lower range value

Unit specified in Set Engr Unit As specified

W

Engr point

Decimal place for user set

0 to 4

2

W

Engr URV

User set upper range value

Unit specified in Set Engr Unit As specified

W

ET disp point

Decimal place for external

temperature

0 to 4

2

W

Flow disp point

Decimal place for flow

0 to 4

2

W

Modify Engr Unit

User set engineering unit

M

Pres disp point

Decimal place for differential

pressure

0 to 4

2

W

Set Engr Unit

Engineering unit select

M

SP disp point

Decimal place for static pressure

0 to 4

2

W

TF disp point

Decimal place for total flow

0 to 4

2

W

Squawk

HART 7

Squawk

Specify the device under the

communication (turn the LCD

on).

M

DP setup

Pres Damp

Damping time constant for DP

0.00 to 100.00 sec

W

Pres Min Span

Minimum span for differential

pressure

R

Pres LRV

Lower range value for differential

pressure

W

Pres LSL

Lower sensor limit for differential

pressure

R

Pres URV

Upper range value for differential

pressure

W

Pres USL

Upper sensor limit for differential

pressure

0 to 4

R

Error log

Error log Clear

Clear error records

M

Error log view

Error records

Log1 (latest) to log4

M

ET setup

ET Damp

Damping time constant for ET

0.00 to 100.00 sec

W

ET Fixed

External temperature fix mode

No,Yes, or FALL BACK

No

W

ET Min Span

Minimum span for external

temperature

R

ET LRV

Lower range value for ET

W

ET LSL

Lower sensor limit for ET

R

ET URV

Upper range value for ET

W

ET USL

Upper sensor limit for ET

R

Fixed ET Val

Temperature value at ET fix mode

20 °C (deg C)

W

*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6

*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)