<3. Parameter Setting>

3-30

IM 01C25R02-01E

Table 3.2

Basic Flow Calc Set-up Steps

Step

Parameter

Contents

Remarks

1

Flow Calc Mode Select Basic Mode

2

Fluid Type

Select liquid or gas

3

Flow Calc Fixed Input Kfactor

Kfactor calculated by Table 3.3 Flow Equation and Kfactor

Calculation

4

Ref SP

Input reference static

pressure

This factor is used for gas.

When fluid type is liquid, set 0 to Ref SP(Spb).

5

Ref Temp

Input reference temperature

6

Temp K1

Input the density rate of

change per temperature

1degC.

This factor is used for mass flow and normal standard volume flow

of liquid. When fluid type is gas or volume flow of liquid, set 0 to

TempK1. Refer to Table 3.4 Symbol

Equation for Basic flow calculation
The flow equation shown in Table 3.3 is applied to the transmitter by combination of fluid type and flow unit

category.

Table 3.3

Flow Equation and Kfactor Calculation

T0310.ai

Mass Flow

Normal-Standard

Volume Flow
Volume Flow

Mass Flow

Normal-Standard

Volume Flow
Volume Flow

Kfactor = /4 × Nc × C / 1- β

4

× ε × d

2

Ч 2 Ч ρb

Qm, Qv or Qv_norm
=

Kfactor × ∆ρ × (1+ Temp K1 × (T-Tb))

Fluid Type Flow unit category

Kfactor

*2

Flow Equation

liquid

Gas

Kfactor = /4 × Nc × C / 1- β

4

× ε × d

2

Ч 2 Ч ρb / ρ norm

Kfactor = /4 × Nc × C / 1- β

4

× ε × d

2

× 2 / ρb

Kfactor = /4 × Nc × C / 1- β

4

× ε × d

2

Ч 2 Ч ρb × 1/K

Kfactor = /4 × Nc × C / 1- β

4

× ε × d

2

Ч 2 Ч ρb × 1/K / ρ norm

Kfactor = /4 × Nc × C / 1- β

4

× ε × d

2

× 2 / (ρb × 1/K)

*1

Qm or Qv_norm
=

Kfactor × ∆ρ × Tb/T × SP/SPb

Qv =

Kfactor × ∆ρ × T/Tb × SPb/SP

*1

*1

*1

mark indicate user input.

*2 Kfactor must be calculated according to the specified flow unit.

Table 3.4

Symbol

No

Symbol

Description

1

Qm

Mass Flow

2

Qv

Volume Flow

3

Qv_norm

Normal-Standard Volume Flow

4

Nc

Unit convert factor

5

Kfactor

Basic flow Calcuration factor

6

C

Discharge Coefficient

7

ε

Expansion Factor

8

β

Diameter Ratio

9

d

Diameter of orifice

10

∆p

Differential Pressure (Transmitter setting unit)

11

ρb

Base Density on Tb, SPb condition

12

ρ norm

Density on Normal, Standard condition

13

Tb

Reference temperature (unit: K)

14

T

Temperature (unit: K)

15

SPb

Reference static pressure (unit: kPa abs)

16

SP

Static Pressure (unit: kPa abs)

17

Temp K1

The density rate of change per temperature 1degC of a density base value (value which set 100%

to 1). For volume flow: set 0.

18

K

Compressibility factor

Note 1. The flow unit is not automatically converted. Refer to IM 01C25R01-01E for Nc calculation.

Note 2. Kfactor, SPb, and Tb are calculated using the equipment setting unit (differential pressure, static pressure, and temperature).

Note 3. Total flow is calculated using the transmitter setting unit.