background image

<3. Parameter Setting>

3-35

IM 01C25R02-01E

a. Burst Command
Select the transmission data at

Burst Command

parameter.

Burst Command

Command parameter

Cmd1: PV

Variable assigned to PV

Cmd2: % range/current % range/current (Percent of

range, Loop current)

Cmd3: Dyn vars/current Process vars/current

(Loop current, PV, SV, TV,

QV)

Cmd9: Device vars

w/Status

Process vars/% range/current

Mapping by user

Cmd33: Device

Variables

Process vars/% range/current

Mapping by user

Cmd48: Read

Additional Device

Status

Self diagnosis information

b. Burst Variable Code
This parameter need to be set when

Burst

Command is Cmd9:Device vars w/Status (up to

eight items) and Cmd33: Device Variables (up to

four items).

• Procedure to call up the display

DD (HART 7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Output condition →HART output →

Burst condition → Burst Message

1,2 or 3 → Burst Device Variables →

Burst Variable Code →

Display Item

Contents

Flow

Select the flow rate

Pres

Select the differential pressure

SP

Select the static pressure

ET

Select the external temperature

Total Flow

Select the total flow

PV

Select the PV value

SV

Select the SV value

TV

Select the TV value

QV

Select the QV value

% rnge

Select the % output

Loop current

Select the output current

Not Used

c. Update period and Max Update Period
Set to

Update Period and Max Update Period.

When the period that is earlier than the operation

period of each process value was set, it is set

automatically to become bigger than an operation

period of EJX multivariable transmitter.

For

Update Period, set the value that is smaller

than

Max Update Period.

• Procedure to call up the display

DD (HART 7)

DTM (HART 7)

[Root Menu] → Detailed setup

→Output condition →HART

output → Burst condition → Burst

Message 1,2 or 3 → Set Burst

Period

→ Update Period

/ Max Update

Period

0.5 s
1 s
2 s
4 s
8 s
16 s
32 s
1 min
5 min
10 min
15 min
30 min
45 min
60 min

d. Burst Msg Trigger Mode
Set the

Burst Msg Trigger Mode from the

parameters shown below.

When

Burst Msg Trigger Mode is Window, Rising

or Falling, set the

Burst Trigger Level.

• Procedure to call up the display

DD (HART 7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Output condition →HART output →

Burst condition → Burst Message 1,2

or 3 → Set Burst Trigger →

Display Item

Contents

Continuous

Burst Message is transmitted

continuously.

Window

In “Window” mode, the Trigger Value

must be a positive number and is the

symmetric window around the last

communicated value.

Rising

In “Rising” mode, the Burst Message

must be published when the source

value exceeds the threshold

established by the trigger value.

Falling

In “Falling” mode, the Burst Message

must be published when the source

value fall below the threshold

established by the trigger value.

On-change

In “On-change” mode, the Burst

Message must be published when the

source value on change established

by the trigger value.