3.3.9 CPU Failure Burnout Direction and

Hardware Write Protect

There are two slide switches on the CPU assembly

board. One sets the burnout direction at CPU

failure, and the other sets a write protection function

which disables parameter changes through

the use of a handheld terminal or some other

communication method.

HIGH

LOW

CPU assembly

Slide switch

Burnout direction switch

Write protection switch

Write Protection

Switch Position

Burnout Direction

Switch Position

BO H

L

WR E

D

H

L

E

D

H

L

E

D

H

L

H

L

Hardware write protection switch (WR)

Burnout direction switch (BO)

Burnout Direction

Write Protection

YES

(Write disabled)

NO

(Write enabled)

F0305.ai

The parameter of

AO alm typ parameter displays

the status of 4-20 mA DC output if a CPU failure

occurs. In case of a failure, communication is

disabled.
Standard specifications or with option code /C3

The burnout direction switch is set to “HIGH”. If a

failure occurs, the transmitter outputs a 110% or

higher signal.
With option code /C1 or /C2

The burnout direction switch is set to “LOW”.

If a failure occurs, a –2.5% or lower output is

generated.
To confirm the burnout direction at the CPU failure,

follow the procedure below.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Output condition → Analog output →

AO alm typ

DTM (HART 5) Configuration → Analog output → AO

alm typ

High

Burnout direction is set to High

Low

Burnout direction is set to Low

3.3.10 Software Write Protection

EJX multivariable transmitter configured data is

saved by using a write protection function. The

write protection status is set to “Yes” when 8

alphanumeric characters are entered in the

New

password field and transferred to the transmitter.
When write protection is set to ”Yes,” the transmitter

does not accept parameter changes. When the

same eight alphanumeric string entered in the

New

password field is also entered in the Enable wrt

10min field and transferred to the transmitter, it

will be possible to change transmitter parameters

during a 10 minute period.
To change the transmitter from the write protection

”Yes” status back to write protection ”No” status,

use

Enable wrt 10min to first release the write

protection function and then enter eight spaces in

the

New password field.

• Procedure to call up the display using DD

(HART 5/HART 7) and DTM (HART 7)

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Device information → Field device

info → Wrt protect menu →

→ Write Protect

Display current protect mode

(Yes: protected, No: not protected)

→ Enable wrt 10

min

Release the protect function for 10

min.

→ New password Set the new password or change

the password

• Procedure to call up the display using DTM

(HART 5)

DTM (HART 5) Write Protect →
→ Write Protect Display current protect mode

(Yes: protected, No: not protected)

→ Enter new

password

Enter the password here to enable

the protect function.

Enter eight spaces to disable the

protect function.

→ Enable write Enter the password here to release

the protect function for 10 min.

3.3.11 Alarm

The function is used to display the alarm codes

when the input differential pressure exceeds the

specified value within the calibration range. The

same is available for the input static pressure,

external temperature, and flow rate. Refer to table

4.5 Alarm Message Summary for the specific alarm

code to be generated.