<3. Parameter Setting>

3-27

IM 01C25R02-01E

• Procedure to call up the display

DTM (HART 5)

Diag and Service → Service →

Loop test →

Display Item

Contents

Manual Test

Set the current value or % value at

Test output value, then click the

Start button.

Auto Test

Set the interval and rate of change

of current output at

Auto Test

Setting, then click the Start button.

(2) DO Test
This function performs the contact and pulse output

test.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Output condition → Process Alerts →

DO config → DO Test →

DTM (HART 5) Diag and Service → Service → DO

test →

Display Item

Contents

Status High

Contact output: OFF

Status Low

Contact output: ON

Frequency

Frequency range 0 to 10,000Hz

Exit

Output test is canceled

(3) Flow Simulation Mode
The flow value can be calculated by using pseudo

values instead of using actual measurements of

differential pressure, static pressure, and external

temperature.
This is called “flow simulation mode.”
The output current value becomes the simulation

value and the LCD continuously displays the

simulation value and alarm (AL.90 SIM) in

alternating sequence.

F0308.ai

Select the desired simulation mode from the list

below, and set the unit and value.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Simulation/Flow Simulation* →

DTM (HART 5) Configuration → Simulation →
→ Simulation

Mode

(Select the

combination

of pseudo

variables)

Off:

ON: DP Differential pressure only
ON: SP Static pressure only
ON: DP

SP

Differential pressure and

static pressure

ON: ET External temperature only
ON: DP

ET

Differential pressure and

external temperature

ON: SP

ET

Static pressure and external

temperature

ON: DP

SP

ET

Differential pressure, static

pressure and external

temperature

Check

Flow

Calc

Differential pressure, static

pressure, and external

temperature without

damping

→ Sim Pres

Unit

Select the unit for the differential

pressure

→ Sim Pres

Set the differential pressure value for

simulation

It is similar about SP and ET.

*: “Simulation” is for HART 5, “Flow Simulation” is for HART 7