2 basic setup, 1 tag and device information, 2 process variable setup – Yokogawa EJX930A User Manual

Page 24: Basic setup -13 3.2.1, Tag and device information -13, Process variable setup -13, 2 basic setup important

Advertising
background image

<3. Parameter Setting>

3-13

IM 01C25R02-01E

3.2 Basic Setup

IMPORTANT

After setting and sending data with the HART

configuration tool, wait 30 seconds before

turning off the transmitter. If it is turned off

too soon, the settings will not be stored in the

transmitter.

3.2.1 Tag and Device Information

If there are specified when ordering, the desired Tag

No. and device information are set and shipped.

Tag No. and device information can be checked as

follows.

• Procedure to call up the display using DD

(HART 5/HART 7) and DTM (HART 7)

Item

Procedure

Tag

[Root Menu] → Basic setup → Tag

Long Tag

(HART 7 only)

[Root Menu] → Basic setup → Long

Tag

Descriptor

[Root Menu] → Basic setup → Device

information → Descriptor

Message

[Root Menu] → Basic setup → Device

information → Message

Date

[Root Menu] → Basic setup → Device

information → Date

• Procedure to call up the display using DTM

(HART 5)

Item

Procedure

Tag

Easy Setup → Tag

or Configuration → HART → Tag

Descriptor

Configuration → Device information 1

→ Descriptor

Message

Configuration → Device information 1

→ Message

Date

Configuration → Device information 1

→ Date

When the Tag No. and device information are

changed, input them based on the following

limitations.

Item

Limitations

Tag

Up to 8 characters or numbers*

1

Long tag

(HART 7 only)

Up to 32 characters or numbers*

2

Descriptor

Up to 16 characters or numbers*

1

Message

Up to 32 characters or numbers*

1

Date

mm/dd/yyyy

- mm: month (2 digits)

- dd: days (2 digits)

- yyyy: years (4 digits)

*1: The characters bounded by the thick line in the following table

can be used.

*2: All characters in the following table can be used.

SP

!

"

#

$

%

&

'

(

)

*

+

,

-

.

/

0

1

2

3

4

5

6

7

8

9

:

;

<

=

>

?

@

A

B

C

D

E

F

G

H

I

J

K

L

M

N

O

P

Q

R

S

T

U

V

W

X

Y

Z

[

\

]

^

_

`

a

b

c

d

e

f

g

h

i

j

k

l

m

n

o

p

q

r

s

t

u

v

w

x

y

z

{

|

}

~

*: SP shows one-byte space

3.2.2 Process Variable Setup

The multivariable transmitter can handle five kinds

of Device Variables; differential pressure (DP),

static pressure (SP), external temperature (ET), and

also flow rate and total flow which are calculated by

using these values.
Four data selected from these five data can be

assigned to Dynamic Variables; PV (Primary

Variable), SV (Secondary Variable), TV (Tertiary

Variable) and 4V* (Fourth Variable) or QV*

(Quaternary Variable).
Data assigned for PV become the 4 to 20mA

current output.
Total flow can not be assigned to PV.

These data are set as follows when the instrument

is shipped.
In case of measurement function code is “A” (Multi

sensing):

PV: Differential pressure

SV: Static pressure

TV: External temperature

4V/QV*: Flow rate

In case of measurement function code is “B” (Mass

flow measurement):

PV: Flow rate

SV: Differential pressure

TV: Static pressure

4V/QV*: External temperature

*: 4V is for HART 5, QV is for HART 7

Advertising
This manual is related to the following products: