<3. Parameter Setting>

3-28

IM 01C25R02-01E

NOTE

The output process value while simulation

can be monitored by LCD and through

communication as follows.

Process value

Output value

DP

Simulation value according to

simulation mode

SP

Simulation value according to

simulation mode

ET

Simulation value according to

simulation mode

Flow Rate

Flow calculation value using the

DP, SP, ET simulation value

Total Flow

Flow Rate accumulation value

Following function is reflected to flow calculation

while simulation.

Simulation

value

Function

DP/SP/ET

Measuring Range (LRV/URV)

Alarm

Status Output

Damping Time*

DP

Low Cut Mode

*: When “Check Flow Calc” is selected, damping is ignored.

If one of the following alarm occurs while

simulation, all of the output data are held to the

value before alarm occurs.

AL.01 (CAP. ERR)

AL.02 (AMP. ERR)

AL.03 (ET. ERR)

(4) Device Variable Simulation Function

(Effective only when setting to HART 7)

Using the simulation function, the output signal can

be confirmed by setting any value and status to the

selected device variable.

Call up the parameter and follow the message

shown.

After completing the step 5, the simulation starts.

Integral indicator shows output and alarm (AL.91)

alternately.

• Procedure of device variable simulation

Step 1 Call up the

parameter

[Root Menu] → Diag/

Service → Test → Simulate

2

Selection of

Device Variable

Select one parameter from

the list below

Off

Flow

Pres

SP

ET

Total Flow

PV

SV

TV

QV

% Range

Loop Current

3

Setting of Value

Input the simulate value

4

Setting of Data

quality

Select one parameter from

the list below

Bad

Poor accuracy

Manual / Fixed

Good

5

Setting of Limit

status

Select one parameter from

the list below

Not limited

Low limited

High limited

Constant

NOTE

• The flow rate is calculated from differential

pressure, static pressure, and external

temperature, and the total flow is

accumulated from the flow rate. Therefore,

the simulation results for the flow rate and

total flow depend on the simulation settings

of differential pressure, static pressure, and

external temperature. The total flow depends

on the flow rate as well.

• The total flow simulation is only applied for

LCD display and communication output and

does not affect the total flow value.

• All the simulations for differential pressure,

static pressure, external temperature,

flow rate are reflected to the output.

Accordingly, the loop current, LCD display,

and communication output are directly

corresponded to the simulate value.

The alarm output is also available according

to the simulate value.

• Damping is applicable for differential

pressure, static pressure, and external

temperature simulation.