12 status output and pulse output, Status output and pulse output -24, Caution – Yokogawa EJX930A User Manual

Page 35

Advertising
background image

<3. Parameter Setting>

3-24

IM 01C25R02-01E

(1) Alarm Setting
Select the process variable at

Process Alert which

the alarm is set, then set the alert mode for that

value.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Output condition → Process Alerts →

DTM (HART 5) Configuration → Process Alerts →
Selection of

the process

variable for

alarm

→ Pres Alert Mode: Differential

pressure
→ SP Alert Mode: Static pressure
→ ET Alert Mode: External

temperature
→ Flow Alert Mode: Flow rate

Selection of

alert mode

Off: Disable the alert function
Hi Al Detect: High side alert detection
Lo Al Detect: Low side alert detection
Hi/Lo Al Detect: High and Low side

alert detection

(2) Threshold Level Setting
Set the threshold of high and low alert value for

alarm generation.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Output condition → Process Alerts →

DTM (HART 5)

Configuration → Process Alerts →

Parameter

Detail

→ Pres Hi Alert

Val

Set the threshold value of upper side

for differential pressure

→ Pres Lo Alert

Val

Set the threshold value of lower side

for differential pressure

→ SP Hi Alert

Val

Set the threshold value of upper side

for static pressure

→ SP Lo Alert

Val

Set the threshold value of lower side

for static pressure

→ ET Hi Alert

Val

Set the threshold value of upper side

for external temperature

→ ET Lo Alert

Val

Set the threshold value of lower side

for external temperature

→ Flow Hi Alert

Val

Set the threshold value of upper side

for flow rate

→ Flow Lo Alert

Val

Set the threshold value of lower side

for flow rate

3.3.12 Status Output and Pulse Output

EJX multivariable transmitter has a contact output.

Select the type of output, status output or pulse

output, and set the unit, value etc.
(1) Selecting of output signal
Status output or pulse output can be selected for

the contact output.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Output condition → Process Alerts →

DO config → DO Signal type

DTM (HART 5) Configuration → Process Alerts → DO

Signal type

Status Output On When Al.

Detect

Output is “ON” when

alert is detected

Off When Al.

Detect

Output is “OFF” when

alert is detected

Pulse Output

Scaled Pulse Scaled pulse output
Frequency

Frequency output

<Example>

Set the status output to output an off signal when

the input pressure exceeds 75 kPa with the alert

mode of Hi. Al Detect.

1) Select “Off When Al. Detect”
2) Select “Pres Alert Mode: Differential pressure” (Refer

to subsection 3.3.11(1) Alarm Setting)

3) Select “Hi Al Detect: High side alert detection” (Refer

to subsection 3.3.11(1) Alarm Setting)

4) Enter “75kPa” to

Pres Hi Alert Val (Refer to subsec-

tion 3.3.11(2) Threshold Level Setting)

CAUTION

Whenever turning on the transmitter or detecting

the short interruption, check if contact output

correctly reflects the alarm status and test

the ON/OFF action of contact output by the

parameter

DO test to confirm that the contact

output operates correctly.

(2) Setting of status output
This feature is used for a transistor output (open

collector) of an on/off signal according to the

status of high and low alarm limits, which are

user-configurable values as shown in subsection

3.3.11 Alarm. The status output can be assigned

as any combination of the high or low limits of

the input pressure, input static pressure, external

temperature, or flow.