Parameter summary, Parameter summary -1 – Yokogawa EJX930A User Manual

Page 83

Advertising
background image

<5. Parameter Summary>

5-1

IM 01C25R02-01E

5. Parameter Summary

Function

Label

Item

Contents

Default value Handling

*

1

Analog output AO alm typ

Analog output alarm type

High or Low

R

AO lower limit

Lower limit of analog output

3.8000 to 21.6000 mA

3.8000 mA

W

AO upper limit

Upper limit of analog output

3.8000 to 21.6000 mA

21.6000 mA

W

Auto recover

Auto-recover from hardware error

Off or On

On

W

Analog output

trim

Clear D/A trim

Reset analog output trim

M

D/A trim

Analog output trim with ammeter

M

Scaled D/A trim

Analog output trim with voltmeter

M

Channel flags

Analog channel flags

0x00

R

Burst mode

Burst mode

Burst mode *

2

Off or On

HART 5

Off or Wired HART Enabled

HART 7

Off

W

Burst option

HART 5

Burst option

Xmtr Variables, PV, % range/

current, Process vars/crnt

W

Burst Xmtr Vals

HART 5

Burst transmitter values

M

Burst Command

HART 7

Burst Command *

2

Cmd 1: PV

Cmd 2: % range/current

Cmd 3: Dyn vars/current

Cmd 9: Device vars w/status

Cmd33: Device Variables

Cmd 48: Read Additional

Device Status.

Cmd 1: PV

W

Burst Variable

Code

HART 7

Device Variable for the Burst

Message *

2

Max 8 slots.

Flow

W

Burst Msg Trigger

Mode

HART 7

Burst Trigger Mode Selection Code

*

2

(Continuous, Window, Rising,

Falling, On-change)

Continuous

R

Set Burst Trigger

HART 7

Configure burst trigger

Configure Burst Msg Trigger

Mode and Burst Trigger Level

M

Set Burst Period

HART 7

Configure burst period

Configure Update Period and

Max Update Period

M

Burst Trigger Level

HART 7

Burst Trigger Level *

2

0.0

R

Update Period

HART 7

Update Period for Burst mode *

2

Update period for burst

message

Burst Message

1: 0.5sec

2: 60sec

3: 60sec

R

Max Update Period

HART 7

Max Update Period for Burst mode

*

2

Maximum update period for

burst message

60 min

R

Date

Date

Date

**/**/**

W

Descriptor

Descriptor

Descriptor

16 alphanumerics

W

*1: Handling: R-Read only, W-Read & Write, M-Method, G-Applicable for option code DG6

*2: Max three Burst Messages (Burst Message 1, Burst Message 2, Burst Message 3)

Advertising