3 detailed setup, 1 analog output signal adjustable range, 2 static pressure setup – Yokogawa EJX930A User Manual

Page 28: 3 external temperature fixation mode, 4 integral indicator scale setup, Detailed setup -17 3.3.1, Analog output signal adjustable range -17, Static pressure setup -17, External temperature fixation mode -17, Integral indicator scale setup -17

Advertising
background image

<3. Parameter Setting>

3-17

IM 01C25R02-01E

3.3

Detailed Setup

3.3.1 Analog Output Signal Adjustable

Range

Output signal adjustable range at normal operating

condition are set as shown below at the factory

when the instrument is shipped, and output signal

are limited by these value.

Lower limit

Upper limit

Standard

Option code /C1

3.8 mA

21.6 mA

Option code /C2 and /C3

3.8 mA

20.5 mA

Output signal range can be changed between

3.8mA and 21.6mA to match it to the equipment on

the receiving side.

Lower value is set at

AO lower limit and upper

value is set at

AO upper limit respectively.

Follow the procedure below to change the upper

and lower values.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Output condition → Analog output →

DTM (HART 5) Configuration → Analog output →
→ AO lower

limit

Set the lower value (mA)

→ AO upper

limit

Set the upper value (mA)

Set the values as below.

Lower value < Upper value

3.3.2 Static Pressure Setup

(1) Selection of Gauge pressure and Absolute

pressure

Either the gauge pressure or absolute pressure can

be selected to display on the LCD display.

Absolute pressure is selected when the instrument

is shipped.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Signal condition → SP Setup →

DTM (HART 5) Configuration → Static Pressure

Sensor →

→ A / G Select Select “Gauge” or “Absolute”

(2) Selection of pressure side
Either the high or low pressure side of capsule can

be selected to monitor the static pressure.

High pressure side is selected when the instrument

is shipped.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Signal condition → SP Setup →

DTM (HART 5) Configuration → Static Pressure

Sensor →

→ SP H/L

Select

Select “High” or “Low”

3.3.3 External Temperature Fixation Mode

The external temperature can be fixed with this

mode. The parameter setting to enter the Fixation

Mode when the RTD sensor is disconnected is also

possible.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Signal condition → ET Setup → Fixed

ET →

DTM (HART 5) Configuration → External

Temperature Sensor →

→ ET Fixed

Select “No”, “Yes” or “FALL BACK”

No: Shows process temperature

value

Yes: Fix the temperature value

FALL BACK: Fix the temperature

value when the RTD

sensor is disconnected.

→ Fixed ET

Val

Set the fixed temperature value

3.3.4 Integral Indicator Scale Setup

The following seven displays are available for

integral indicator. A cycle of up to four displays can

be shown by assigning variables to the parameters

at

Disp select.

• % of PV range

• Flow rate

• Input differential pressure

• Input static pressure

• Input external temperature

• User set scaled PV

• Total flow

Advertising
This manual is related to the following products: