<4. Diagnostics>

4-10

IM 01C25R02-01E

B

A

A

A

B

B

B

A

F0406.ai

Diag Supp Count (Number of times: 3)

Diag Supp Count (Number of times: 3)

Diag Period

Diag Period

Upper Threshold

(Ex.

Lim fDPmax)

Lower Threshold

(Ex.

Lim fDPmin)

An alarm is generated.

An alarm is generated.

Time

Time

Figure 4.4

Relationship of Diag Supp Count and

Alarm

The number of detection to give an alarm is set for

each blockage detection function. The default value

at the shipment is set to three times.
If fluctuating around the threshold value, an alarm

may be often generated. In this case, change the

threshold value (Limit parameter) or the sampling

time (

Diag Period) to enhance the accuracy of the

blockage detection. Refer to subsection 4.2.2.10.