<3. Parameter Setting>

3-15

IM 01C25R02-01E

NOTE

The calibration range can be set as PV LRV >

PV URV under the following conditions,

reversing the 4 to 20 mA output signal.

PV LSL -10% of USL ≤ PV LRV ≤ PV USL

+10% of USL

PV LSL -10% of USL ≤ PV URV ≤ PV USL

+10% of USL

|PV URV - PV LRV| ≥ PV Min. Span

If PV is flow, PV LRV and PV URV must be the

following conditions.

0 ≤ PV LRV

0 ≤ PV URV

PV LRV < PV URV

The flow range is set to LRV=0 and URV=100

when the Flow calc mode is changed to Basic

mode or Full Auto mode.
If PV is ET, PV LRV and PV URV must be the

following conditions.

-210°C ≤ PV LRV ≤ 860°C

(-346°F ≤ PV LRV ≤ 1580°F)

-210°C ≤ PV URV ≤ 860°C

(-346°F ≤ PV URV ≤ 1580°F)

|PV URV - PV LRV| ≥ PV Min. Span

3.2.4 Units

Refer to the subsection 3.2.3 to call up the display.

Select the unit from displayed list as shown below.

(1) Unit list of differential pressure

mmH2O, mmH2O@68degF, mmHg, Torr, MPa,

kPa , Pa, mbar , bar , gf/cm2, kgf/cm2, inH2O,

inH2O@68degF, inHg, ftH2O, ftH2O@68degF, psi,

atm, hPa

Note that the Yokogawa default setting for the

standard temperature is 4°C (39.2°F). For the units

of mmH

2

O, inH

2

O, and ftH

2

O, the pressure varies

according to the standard temperature definition.

Select the appropriate unit with @68degF when a

standard temperature of 20°C (68°F) is required.
(2) Unit list of static pressure

mmH2O, mmH2O@68degF, mmHg, Torr, MPa,

kPa , Pa, mbar , bar , gf/cm2, kgf/cm2, inH2O,

inH2O@68degF, inHg, ftH2O, ftH2O@68degF, psi,

atm, hPa

(3) Unit list of temperature

degC , degF, Kelvin

*

*: In the case of using DTM(HART 7), it is displayed as “K“.

(4) Unit list of flow

Mass Flow g/s, g/min, g/h, kg/s, kg/min, kg/h,

kg/d, t/min, t/h, t/d, lb/s, lb/min, lb/h,

lb/d, STon/min, STon/h, STon/d,

LTon/h, LTon/d

Normal/

Standard

Volume

Flow

Nm3/h, NL/h, SL/h, SL/min, SL/s,

Nm3/d, SCFD, SCFH, SCFM, SCFS,

Sm3/d, Sm3/h, MSCFD, MMSCFD

Volume

Flow

CFM, GPM, L/min, Impgal/min, m3/h,

gal/s, Mgal/d, L/s, ML/d, CFS, ft3/d,

m3/s, m3/d, Impgal/h, Impgal/d, CFH,

m3/min, bbl/s, bbl/min, bbl/h, bbl/d,

gal/h, Impgal/s, L/h, gal/d

(5) Unit list of total flow

g, kg, t, lb, Ston, Lton, oz, gal, L, Impgal, m3,

bbl, yd3, ft3, in3, Nm3, NL, SCF, Spcl*

* The user unit is displayed on LCD.

To configure the user unit, refer to subsection 3.3.5.

3.2.5 Damping Time Constant Setup

Any number from 0.00 to 100.00 can be set for

the amplifier damping time constant of process

variables.
Refer to subsection 3.2.3 to call up the display.
Damping time constant is set as shown in the

following table at the factory when the instrument

is shipped, but in case of the option code /CA is

specified, the damping time constant is set as

specified in the order.

Process variables

Factory default value

Differential pressure

2sec

Static pressure

1sec

External temperature

2sec

Flow rate

0sec

NOTE

• When the HART communication is used

under the condition of quick output change,

set the damping time constant more than 0.5

sec.

• The damping time constant for the amplifier

assembly can be set here. The damping time

constant for the entire transmitter is the sum

of the values for the amplifier assembly and

the capsule assembly.

About the value for the capsule assembly,

refer to the User’s Manual for EJX910/

EJX930 (IM 01C25R01-01E) or General

Specifications (GS 01C25R01-01E, GS

01C25R04-01E).