<4. Diagnostics>

4-25

IM 01C25R02-01E

Integral

indicator

HART configuration

tool display

Cause

4-20mA Output

operation during error

Countermeasure

Status

group

*

1

Diagnostic

List

group *

2

AL. 55

SP. ADJ

SP SPAN trim err *

1

Static Pressure SPAN

Trim Error *

2

Specified value is outside

of setting range.

Continues to operate and

output.

Adjust settings and

change them as

needed.

7

C

on

fig

ur

at

io

n

SP ZERO trim err *

1

Static Pressure ZERO

Trim Error *

2

AL. 56

ET. RNG

Illegal ET LRV *

1

Illegal External Temp

LRV *

2

Holds at the output value

that existed immediately

before the error occurred.

Check settings and

change them as

needed.

8

Illegal ET URV *

1

Illegal External Temp

URV *

2

Illegal ET SPAN *

1

Illegal External Temp

SPAN *

2

AL. 57

ET. ADJ

ET SPAN trim err *

1

External Temp SPAN

Trim Error *2

Continues to operate and

output.

Adjust settings and

change them as

needed.

7

ET ZERO trim err *

1

External Temp ZERO

Trim Error *

2

AL. 58

FL. ADJ

F set outside Range *

1

Flow set Outside

Range *

2

Specified value is outside

of setting range.

Holds at the output value

that existed immediately

before the error occurred.

Check settings and

change them as

needed.

8

AL. 59

PLS.ADJ

PLS set err *

1

, *

2

Specified value is outside

of setting pulse output.

Normal calculation.

7

ET Fixed Mode *

1

, *

2

Under Temperature Fix

Mode. PV is ET

Temp. Output Fix at 4mA.

Leave from

Temperature Fix

Mode.

7

AL. 79

OV. DISP

Displayed value exceeds

limit.

Continues to operate and

output.

Check settings and

change them as

needed.

D

ia

g

St

at

us

AL.87

FLG. HI

FT high alarm *

1

Flg Temp High Alarm

*

2

Flange temperature

exceeds a preset upper

limit.

It depends on the Diag Out

Option setting.

Off: Continue to operate and

output.

Burnout:Outputs AO upper

limit or AO lower limit.

Fall back:Outputs Diag Out

Fixed Val.

Check the heater

failure.

Check the capsule

temp. and Amplifier

temp.

Adjust Flg Temp

Coef.

9

AL.87

FLG. LO

FT low alarm *

1

Flg Temp Low Alarm

*

2

Flange temperature is

below a preset lower

limit.

AL.88

INVR.DP

Invalid Ref DP *

1

Invalid Ref fDP *

2

Differential pressure/

pressure fluctuation does

not reach the reference

level required to blockage

detection so that no

blockage detection is

carried out.

Continue to operate and

output.

Check process

condition.

AL.88

INVR.SL

Invalid Ref SPL *

1

Invalid Ref fSPl *

2

Low-pressure-side

fluctuation does not

reach the reference

fluctuation level required

to blockage detection.

AL.88

INVR.SH

Invalid Ref SPH *

1

Invalid Ref fSPh *

2

High-pressure-side

fluctuation does not reach

the reference fluctuation

level required to blockage

detection.

AL.88

INVR.F

Invalid Ref F *

1

Invalid Ref BlkF *

2

BlkF can not be used for

blockage detection for

some reasons.

AL.89

ILBD.OV

ILBD over range *

1

Outside Diagnosis

Range *

2

Appointed the diagnosis

range outside.

*1: DD (HART 5/HART 7), DTM (HART 7)

*2: DTM (HART 5)

*3: Available only for HART 7