6 condition check, 6 condition check -14 – Yokogawa EJX930A User Manual

Page 64

Advertising
background image

<4. Diagnostics>

4-14

IM 01C25R02-01E

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Diag/Service → Diag

Parameters → Diag Output → Diag

Fixed Out Val →

DTM (HART 5) Diag and Service → Advanced Diag

Configurations → Diag Output → Diag

Out Option →

Status Output for Advanced diagnostic

The output of the abnormal results are applicable

for a transistor output (open collector) of an on/off

signal according to the status of high and low alarm

limits, which are values set to Limit parameters as

shown in subsection 4.2.2.1. About the

Flg temp Hi

Alert Val, or Flg temp Lo Alert Val for Heat trace

monitoring, refer to subsection 4.2.3.2.

DO Select

If the advanced diagnostic function is installed, the

following modes can be also assigned to the status

output in addition to Pres, SP, Temp and Flow.

Mode

Function

Diag Alarm The status regarding advanced diagnostic

masked by

Diag Option is output.

All

All status of Press, SP, Temp, Flow and

advanced diagnostic are output.

Alarm Display on LCD

If the ILBD algorithm detects the abnormality, the

content of the detected result is displayed with

“AL.88” or “AL.89” on the LCD. “AL.88” indicates

that condition is not applicable for the abnormality

detection and “AL.89” indicates the abnormality is

detected.

F0410.ai

Figure 4.7

Display Example of H Side Blocking

The alarm display on LCD regarding the advanced

diagnostic is described in Table 4.5.

NOTE

The alarms of “Invalid Ref xx” and “ILBD over

range” do not link to the 4-20 mA analog signal

and Status output.

4.2.2.6 Condition Check

After the EJX multivariable transmitter was

installed, it is necessary to confirm if

Pres is

stable under the normal operating condition or if

fluctuation amplitude under the normal operating

condition is large enough to detect the blockage.

Stability of Pressure Value

1) Observe the value change of

Pres under the

normal operating condition for 10 minutes.

2) Confirm the value change is less than 10%.

• Procedure to call up the display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Sensors → Pres

DTM (HART 5) Configuration → Process Input → Pres

If the value change is more than 10%, the error

influences pressure fluctuation value so that the

blockage detection becomes impossible. Consider

the plant operating conditions.

Fluctuation Value

NOTE

The blockage detection may not be carried

out correctly when pressure fluctuation

amplitude especially with the pressure and level

measurement, is small.

Confirm that each value of

fDP, fSPl, fSPh, and

BlkF is more than the value specified in the below

table.

• Procedure to call up the

fDP, fSPl, fSPh display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Diag/Service → Diag

Parameters → ILBD parameters →

Status → Fluct Variables → fDP/fSPl/

fSPh

DTM (HART 5) Diag and Service → Advanced Diag

Variables → fDP/fSPl/fSPh

• Procedure to call up the

BlkF display

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Diag/Service → Diag

Parameters → ILBD parameters →

Status → Diag Variables → BlkF

DTM (HART 5) Diag and Service → Advanced Diag

Variables → BlkF

Table 4.4

Requirements to apply ILBD

Condition

fDP

7×10

-10

or more

fSPI

1×10

-10

or more

fSPh

1×10

-10

or more

BlkF

-0.5 to 0.5