A-12 – Yokogawa RotaMASS 3-Series User Manual

Page 112

Advertising
background image

APPENdIX 1. LIST OF PArAMETErS FOr EACH BLOCK OF rOTAMASS

a-12

IM 01R04B05-00E-E 3rd edition July 30, 2010 -00

all Rights Reserved. Copyright © 2005, Rota Yokogawa

relative

Index

Index

Parameter Name

Factory default

Write

Mode

Explanation

91

2091

FtC1

*)

o/S

Defines a linear temperature coefficient of
the frequency at roh = 1.
the valid range and the default value de-
pend on the selected sensor model.

92

2092

FtCK

*)

o/S

Defines a quadratic temperature coefficient
of the frequency at roh = 1.
the valid range and the default value de-
pend on the selected sensor model.

93

2093

SKP

*)

o/S

Defines a linear pressure coefficient of the
sensor constant SK20.
the valid range and the default value de-
pend on the selected sensor model.

94

2094

FPC

*)

o/S

Defines a linear pressure coefficient of the
frequency.
the valid range and the default value de-
pend on the selected sensor model.

95

2095

SKtK

*)

o/S

Defines a quadratic temperature coefficient
of the sensor constant SK20.
the valid range and the default value de-
pend on the selected sensor model.

96

2096

SKPt

*)

o/S

Defines a quadratic pressure coefficient of
the sensor constant SK20.
the valid range and the default value de-
pend on the selected sensor model.

97

2097

FPtC

*)

o/S

Defines a temperature - pressure coefficient
of the frequency.
the valid range and the default value de-
pend on the selected sensor model.

98

2098

FQC1

*)

o/S

Defines a linear flow coefficient of the fre-
quency.
the valid range and the default value de-
pend on the selected sensor model.

99

2099

FQC2

*)

o/S

Defines a quadratic flow coefficient of the
frequency.
the valid range and the default value de-
pend on the selected sensor model.

100

2100

PRESSuRE

0.0 bar

o/S

Sets the pressure value for correction with
SKP and FPC.

101

2101

PRESSuRE_unIt

bar

o/S

this parameter shows the unit of
PRESSuRE; range bar or psi.

102

2102

SLuG_aLaRM_SELECt

not apply

o/S

this parameter enables the following functions.
DRIVE_GaIn,
SLuG_CRItERIa
SLuG_DuRatIon
aFtER_SLuG
DRIVE_GaIn_DaMPInG
When the value is “not apply”, they do not
perform.
When the value is “apply”, they perform.
If gas measurement is ordered, this parameter
is not available. the value is “not apply”.

103

2103

DRIVE_GaIn

-

-

this parameter indicates a drive gain value.
When the value of SLuG_aLaRM_SELECt
is “not apply” this function does not perform.

104

2104

SLuG_CRItERIa

11 V

o/S

this parameter indicates a level of drive
gain when an alarm should happen. When
the value of SLuG_aLaRM_SELECt is
“not apply”, users can not change this
value. Range 0 to 11 V.

*) Depends on detector size. For RCCF31 not combined with detector, data for RCCS36 are stored.