APPENdIX 6. SOFTWArE dOWNLOAd

a-60

IM 01R04B05-00E-E 3rd edition July 30, 2010 -00

all Rights Reserved. Copyright © 2005, Rota Yokogawa

A6.8 resource Block’s Parameters relating to Software

download

table a6.3 additional Parameters of Resource Block

TA0103.EPS

Relative

Index

Index

Parameter Name

(Factory Set)

Write

Mode

Description

SOFTDWN_PROTECT

1, 0, 0, 0, 0, 0,
0, 0, 0

SOFTDWN_ACT_AREA

Defines whether to accept software download
0x01: Unprotected
0x02: Protected

Selects the software download method.
0x01: Standard

Indicates the number of times the internal
FlashROM was erased.

Indicates the ROM number of the currently
working FlashROM.
0: FlashROM #0 working
1: FlashROM #1 working

Indicates the software module revision.

Indicates an error during a software downloa
See Table A6.4.

1057

1055

1056

SOFTDWN_MOD_REV

1054

1053

0

SOFTDWN_FORMAT

SOFTDWN_COUNT

0x01

0x01

0

56

57

55

54

53

1058

SOFTDWN_ERROR

0

58

A6.7 Troubleshooting

For information on the download tool’s error messages, see also the software’s user’s Manual.
Table A6.2 Problems after Software Update

Symptom

Cause

Remedy

an error occurs before starting a
download, disabling the
download.

the selected download file is not for the
selected field device.

Check SoFtDWn_ERRoR in the resource
block and obtain the correct file.

an error occurs after starting a
download, disabling the
download.

You attempted to update the device revision
by downloading a file which is not an original
file.

Check SoFtDWn_ERRoR in the resource
block and obtain the original file.

the selected field device does not support
software downloading.

Check whether the option code /EE is
included in the model and suffix codes of the
device.

the voltage on the fieldbus segment falls
below the specified limit (9 volts).

Check the capacity of the field bus power
supply used and the voltage at the terminal.

there was an error in a checksum or the
number of transmission bytes.

Check SoFtDWn_ERRoR in the resource
block and obtain the correct file.

the download takes far longer
than expected or fails frequently.

the fieldbus segment is noisy.

an error occurs after activation.

Check the noise level on the fieldbus
segment.

transient error caused by the internal
resetting of the field device

Check whether communication with the field
device has recovered after a while.

the new software does not work
after the activation.

the file of the current revision was
downloaded.

obtain the correct file.

Failure of the memory in field device, etc.

Check SoFtDWn_ERRoR in the resource
block, and re-try downloading.
If fails, place a service call.

ta0102.EPS

the download tool does not allow download
with same software revision.

Check the setting of the download tool.