9. EXPLOSION PrOTECTEd TyPE INSTrUMENTS

9-10

IM 01R04B05-00E-E 3rd edition July 30, 2010 -00

all Rights Reserved. Copyright © 2005, Rota Yokogawa

9.2.2 Installation

Integral type RCCt3 :

L/+
N/-
G

Power supply

I/O control

Hazardous area

Safe area

I/O

Rotamass RCCT3

F91.EPS

Terminal Box

NOTE

temperature classification :the remote converter RCCF31 has a t6 temperature class rating for operation

at ambient temperature up to +50°C / +122°F:

RCCS30 to RCCS33

without insulation

RCCS30 to RCCS33

with factory insulation

temp.

class

Max. ambient

temperature

Max. process

temperature

Max. ambient

temperature

Max. process

temperature

t6

50°C / 122°F

60°C / 140°F

60°C / 140°F

60°C / 140°F

t5

50°C / 122°F

80°C / 176°F

80°C / 176°F

90°C / 194°F

t4

80°C / 176°F
50°C / 122°F

100°C / 212°F
120°C / 248°F

80°C / 176°F

130°C / 266°F

t3

80°C / 176°F

150°C / 302°F

80°C / 176°F

150°C / 302°F

t2

80°C / 176°F

150°C / 302°F

80°C / 176°F

150°C / 302°F

RCCS34 to RCCS39/XR

without insulation

RCCS34 to RCCS39/XR

with factory insulation

RCCt34 to RCCt39/XR

temp.

class

Max. ambient

temperature

Max. process

temperature

Max. ambient

temperature

Max. process

temperature

Max. ambient

temperature

Max. process

temperature

t6

40°C / 104°F

40°C / 104°F

65°C / 149°C

65°C / 149°F

50°C / 122°F

65°C / 149°C

t5

55°C / 131°F

55°C / 131°F

75°C / 167°F

75°C / 167°F

50°C / 122°F

80°C / 176°F

t4

80°C / 176°F
40°C / 104°F

100°C / 212°F
120°C / 248°F

70°C / 158°F

115°C / 239°F

50°C / 122°F

115°C / 239°F

t3

80°C / 176°F
40°C / 104°F

160°C / 320°F
180°C / 356°F

70°C / 158°F

180°C / 356°F

50°C / 122°F

150°C / 302°F

t2

80°C / 176°F

220°C / 428°F

65°C /149°F

275°C / 527°F

t1

45°C / 113°F

350°C / 662°F

For customer insulation of RCCS34 to 39/IR the following must be regarded :

the table "with factory insulation" is calculated with 80 mm insulation and k-factor = 0.4 W/m

2

K.

If your insulation data are worse than these use table "without insulation" !