APPENdIX 1. LIST OF PArAMETErS FOr EACH BLOCK OF rOTAMASS

a-20

IM 01R04B05-00E-E 3rd edition July 30, 2010 -00

all Rights Reserved. Copyright © 2005, Rota Yokogawa

Table A2.1 INTEG_TyPE

name

Integration Method

Integration Range

Reset trigger (Reset if one of the
following conditions is established)

trip output

uP_auto(1) Counting up

Starting from "0"

-InF< total <totaL_SP

0< atotal <+InF

0< Rtotal <+InF

-InF< acctotal <+InF

• out reaches totaL_SP.

• RESEt_In = 1

• oP_CMD_Int = 1

s

uP_DEM(2)

Counting up

Starting from "0"

-InF< total <+InF

0< atotal <+InF

0< Rtotal <+InF

-InF< acctotal <+InF

• RESEt_In = 1

• oP_CMD_Int = 1

s

Dn_auto(3)

Counting down

Starting from

totaL_SP

0< total <+InF

0< atotal <+InF

0< Rtotal <+InF

-InF< acctotal <+InF

• out reaches "0."

• RESEt_In = 1

• oP_CMD_Int = 1

s

Dn_DEM(4)

Counting down

Starting from

totaL_SP

-InF< total <+InF

0< atotal <+InF

0< Rtotal <+InF

-InF< acctotal <+InF

• RESEt_In = 1

• oP_CMD_Int = 1

s

PERIoDIC(5) Counting up

Starting from "0"

-InF< total <+InF

0< atotal <+InF

0< Rtotal <+InF

-InF< acctotal <+InF

• at the period specified by

CLoCK_PER

• oP_CMD_Int = 1

3

DEManD(6)

Counting up

Starting from "0"

-InF< total <+InF

0< atotal <+InF

0< Rtotal <+InF

-InF< acctotal <+InF

• RESEt_In = 1

• oP_CMD_Int = 1

3

PER&DEM(7)

Legend s: trip output is made. 3: no trip output is made.

Counting up

Starting from "0"

-InF< total <+InF

0< atotal <+InF

0< Rtotal <+InF

-InF< acctotal <+InF

• at the period specif. by CLoCK_PER

• RESEt_In = 1

• oP_CMD_Int = 1

3

ta0203.EPS