5. CONFIGUrATION

5-6

IM 01R04B05-00E-E 3rd edition July 30, 2010 -00

all Rights Reserved. Copyright © 2005, Rota Yokogawa

5.6.2 Trend Objects

It is possible to make settings so that a function
block automatically transmits the trend. For this,
each RotaMaSS has ten trend objects: eight for
trends of analog parameters and two for discrete
parameters. For each trend object, specify a sin-
gle parameter, the trend of which is to be trans-
mitted. Each
trend object has the parameters listed in table
5.8. For the first four parameters, setting is
mandatory. Before writing parameter settings to
a trend object, parameter WRItE_LoCK of the
resource block must be modified to unlock the
write-lock.
Table 5.8 Parameters for Trend Objects

T0508.EPS

S

ub

-

index

P

arameters

D

escription

1

Block Index

Sets the leading index of
the function block that
takes a trend.

2

Parameter Relative
Index

Sets the index of parameters
taking a trend by a value
relative to the beginning of the
function block. In the
Rotamass, the following three
types of trends are possible.
7: PV
8: OUT
19: FIELD_VAL

3

Sample Type

Specifies how trends are
taken. Choose one of the
following 2 types:

1: Sampled upon

execution of a function
block.

2: The average value is

sampled.

4

Sample Interval

Specifies sampling
intervals in units of 1/32
ms. Set the integer
multiple of the function
block execution cycle.

5

Last Update

The last sampling time.

6 to 21

List of Status

Status part of a sampled
parameter.

21 to 37 List of Samples

Data part of a sampled
parameter.

ten trend objects are not factory-set.
Table 5.9 Trend Objects

T0509.EPS

Index

Parameter

Factory Setting

32000 to

32007

32008

32009

TREND_DIS. 1

TREND_DIS. 2

TREND_FLT.1 to

TREND_FLT.8

Not set.

Not set (these parameters
are used with a DI block or
optional PID block).

F0505.EPS

AI2 OUT

AI1 OUT

FBOD

Alert

Trend

VCR

DLSAP
DLCEP

Fieldbus Cable

ROTAMASS

0xF8 0xF3 0xF4 0xF7 0xF9 0x20

0x07

#1

#2

#3

#4

#8

#6

#7

#5

#1

#3

#2

DI2

OUT

DI1

OUT

System
Management
Information
Base (SMIB)

Network
Management
Information
Base (NMIB)

Resource

block

Transducer

block

Link object

Host 1

Host 2

Device

Figure 5.5 Examle of default Configuration

5.6.3 View Objects

View objects are used to group parameters. this
reduces the load of data transactions. Each
RotaMaSS supports four view objects for each
of the resource block, transducer block, six aI
blocks, two It blocks, and PID block (optional).
Each view object contains a group of the param-
eters listed in tables 5.11 to 5.14.
Table 5.10 Purpose of Each View Object

VIEW_1

VIEW_2

VIEW_3

VIEW_4

Set of all the dynamic parameters.

Description

Set of dynamic parameters required by operator
for plant operation. (PV, SV, out, Mode etc.)

Set of static parameters which need to be
shown to plant operator at once. (Range etc.)

Set of static parameters for configuration or
maintenance.

t0510.EPS

Advertising