A7.3 transfer of las, A-66 – Yokogawa RotaMASS 3-Series User Manual

Page 166

Advertising
background image

APPENdIX 7. LINK MASTEr FUNCTIONS

a-66

IM 01R04B05-00E-E 3rd edition July 30, 2010 -00

all Rights Reserved. Copyright © 2005, Rota Yokogawa

A7.3 Transfer of LAS

there are two procedures for an LM to become the LaS:

• If the LM whose value of [V(St)V(tn)] is the smallest on a segment, with the exception of the current

LaS, judges that there is no LaS on the segment, in such a case as when the segment has started up
or when the current LaS has failed, the LM declares itself as the LaS, then becomes the LaS. (With
this procedure, an LM backs up the LaS as shown in the following figure.)

• the LM whose value of [V(St)V(tn)] is the smallest on a segment, with the exception of the current

LaS, requests the LaS on the same segment to transfer the right of being the LaS, then becomes the
LaS.

LM

node address:

0x15

Slottime = 5

LM

node address:

0x16

Slottime = 5

node address: 0x10
Slottime = 5

Basic device

node address:

0xF1

Basic device

node address:

0xF2

Basic device

node address:

0xF3

Basic device

node address:

0xF4

LaS

LaS

In the event that the current LaS in
this segment (node address 0x10)
fails, the LM with the address of 0x15
takes its place to become the LaS.

LM

Fa0602.EPS

Figure A7-2. Backup of LAS

to set up a RotaMaSS as a device that is capable of backing up the LaS, follow the procedure below.

notE: When changing the settings in a
RotaMaSS, add the RotaMaSS to the segment
in which an LaS is running. after making chang-
es to the settings, do not turn off the power to the
RotaMaSS for at least 60 seconds.

(1) Set the node address of the RotaMaSS. In

general, use an address from 0x10 to

[V(Fun) – 1].

not used

LM device

not used

Basic device

Default address

Portable-device address

V (Fun)

V (Fun) + V (nun)

V (nun)

0xFF

0xFD

0xFC

0xF8

0xF7

0x10

0x00

Fa0603.EPS

Figure A7-3. Node Address ranges

(2) In the LaS settings of the RotaMaSS, set

the values of V(St), V(MRD), and V(MID) to
the same as the respective lowest capability
values in all the devices within the segment.
an example is shown below.

Sub-

index

Element

Device

1

Device

2

Device

3

Description

1

3

6

Slottime

MaxResponse
Delay

MinInterPdu

Delay

4

3

4

8

6

8

10

3

12

20

5

10

Capability value
for V(St)

Capability value
for V(MRD)

Capability value
for V(MID)

ta0601.EPS

DlmeBasicInfo (Rotamass Index xxx (SM)

Rota-

mass

In this case, set Slottime, MaxResponsetime,
and MinInterPduDelay as follows:

Subinde x

Element

Configu redLink Settings Record

(Rotamass Index xxx (SM)

Description

Setting

(Default)

V (St)

V (MRD)

V (MID)

20

6

12

(4095)

(5)

(12)

Slottime

MaxResponseDelay

MinInterPduDelay

1

3

6

ta0602.EPS

(3) In the LaS settings of the RotaMaSS, set

the values of V(Fun) and V(nun) so that they
include the node addresses of all nodes within
the same segment. (See also Figure a7-3.)