A5.18 alarms, A5.19 example of block connections, A5.18.1 block alarm (block_alm) – Yokogawa RotaMASS 3-Series User Manual

Page 155: A5.18.2 process alarms

Advertising
background image

APPENdIX 5. PId BLOCK

a-55

IM 01R04B05-00E-E 3rd edition July 30, 2010 -00

all Rights Reserved. Copyright © 2005, Rota Yokogawa

* the modes to which a PID block can transfer

are limited to those set in MoDE_BLK.permit-
ted, and the priority levels of modes are as
shown below. In fact, if normal shed, normal
return is set for SHED_oPt, detection of a
computer failure causes MoDE_BLK.actual to
change to CaS, auto, or Man, whichever is
set in MoDE_BLK.permitted and has the low-
est priority level.

Man

Higher priority level

auto
CaS
RCaS
Rout

Lower priorty level

** only if auto is included in MoDE_BLK.permit-

ted. If the block upstream of the PID block in
question is a control block, mode transitions
of the PID block to CaS occur in the following
sequence due to initialization of the cascade
connection: RCaS or Rout ∅ auto ∅ CaS.

A5.18 Alarms

there are two kinds of alarms generated by a PID
block: block and process alarms.

A5.18.1 Block Alarm (BLOCK_ALM)

the block alarm BLoCK_aLM is generated upon
occurrence of either of the following errors (values
set in BLoCK_ERR) and notifies the content of
BLoCK_ERR.

Value of

BLoCK_ERR

Condition

In.status of the PID block is either of the
following:
• Bad-Device Failure
• Bad-Sensor Failure

MoDE_BLK.target of the PID block is o/S.

Input Failure


out of Service

ta0511.EPS

A5.18.2 Process Alarms

there are six types of process alarms. only one
process alarm can be generated at the same
time, and the process alarm having the highest
priority level from among those occurring at the
same time is generated. the priority level is set
for each process alarm type.

Parameter

Containing

Priority

Level Setting

Cause of occurrence

Process

alarm

occurs when the PV increases
above the HI_HI_LIM value.

occurs when the PV increases
above HI_LIM value.

occurs when the PV decreases
below the Lo_LIM value.

occurs when the PV decreases
below the Lo_Lo_LIM value.

occurs when the value of
[PV - SP] increases above the
DV_HI_LIM value.

occurs when the value of
[PV - SP] decreases below the
DV_Lo_LIM value.

HI_HI_PRI

HI_PRI

Lo_PRI

Lo_Lo_LIM

DV_HI_PRI

DV_Lo_PRI

HI_HI_aLM

HI_aLM

Lo_aLM

Lo_Lo_aLM

DV_HI_aLM

DV_Lo_aLM

ta0512.EPS

A5.19 Example of Block

Connections

PID

BKCaL_In

out

In

ao

BKCaL_out

CaS_In

aI

out

Fa0506.EPS