IM DA100-01E

2-9

2

Installation and Wiring

2.4 Connecting the Interface Cables

Connecting the RS-232C cable

Connect the connector of the RS-232C communication module to a personal computer as follows.
The figures below show cases when hardware handshake is carried out. For other connections,
refer to the DA100 Communication Interface User’s Manual (IM DA100-11E).

• In case of IBM compatible DOS machine

D-Sub 25 pin

D-Sub 9-pin

FG

SD

RD

CS

DR

ER

FG

SD

RD

CS

DR

ER

PC side

Module side

SG

SG

RS

RS

6

5

4

3

2

1

20

7

6

5

4

3

2

1

20

7

SD

RD

CS

DR

ER

SD

RD

CS

DR

ER

PC side

Module side

SG

SG

RS

RS

20

7

6

5

4

3

2

4

5

6

8

7

2

3

CAUTION

When (dis)connecting the RS-232C cable, turn OFF the power of both the
personal computer and the data acquisition unit DA100. If the power is not
turned OFF, malfunctions may occur and the internal circuitry may be
damaged.

Note

To eliminate noise, we recommend to apply ferrite cores to both ends of the interface cable (e.g.

ZCAT3035-1330 from TDK). If the noise persists, apply more ferrite cores. Use shielded interface cables
and ground equipment together at one point.

Personal
computer

DA100

Ferrite core

Function grounding