Transportation and Storage Conditions

These refer to the environmental conditions existing during transportation and storage from the
time of shipment from the factory until commencement of use, and also during transportation and
storage in case of temporary non-use. If the environmental conditions are maintained within the
specified range, the unit will not incur permanent damage, and can be returned to a normal
working condition (re-adjustment may be required in some cases.)

Ambient temperature

–25 to 60

°C

Humidity

5 to 95% RH

Vibration

10 to 60 Hz 4.9m/s

2

max.

Shock

392 m/s

2

max (in packed condition)

Other Specifications

Clock

With calendar function; be sure to set when the power is ON.

Clock accuracy

±100ppm

System alarm

Contact output (when DI/DO is connected)

Back-up of setting parameters

Lithium battery back-up (approx. 10 years), excluding clock function (time and date are reset to
96/1/1 0:00 each time the power is turned ON.)

Insulation resistance

At least 20M

Ω between each terminal and ground (at 500 VDC)

Withstand voltage

· Between AC power supply terminal and case of DA100 main unit:

1500 VAC (50/60Hz) for one minute

· Between AC power supply terminal and the case of the subunit:

1500 VAC (50/60Hz) for one minute

· Between DC power supply terminal and the case of DA100 main unit:

1000 VAC (50/60Hz) for one minute

· Between DC power supply terminal and the case of the subunit:

1000 VAC (50/60Hz) for one minute

· Between input teminal and case of DA100 main unit:

1500 VAC (50/60Hz) for one minute

· Between output teminal and case of DA100 main unit:

2300 VAC (50/60Hz) for one minute

EMC Conformity Standards

· Emission

EN55011: Class A

· Immunity

EN50082-2

IEC1000-4-2 Electrostatic Discharge

Performance Criteria A*

8kV(Air), 4kV(Contact)

IEC1000-4-3 Radiated fields

Performance Criteria A*

80 to 1000MHz, 10V/m

IEC1000-4-4 Fast Transients

Performance Criteria B

Power line 2kV, The others 1kV

IEC1000-4-6 Conducted Disturbance

Performance Criteria A*

0.15 to 80MHz, 10V

* Effect on accuracy

Universal input module and DCV/TC/DI input module

±10% of range (except for 50V range)

±20% of range (50V range)
When the extension module is used

±20% of range (except for 50V range)

±40% of range (50V range)
Strain input module
±10% of range (except for 2000 µε range)

±50% of range (2000 µε range)
Other input module

±10% of range

4.1 DA100/ DS400/ DS600